Pressure limit
Default
No
KP level
Default
7
TV level
Default
Turn
®
Code
16/17/18
Press
, Code 16/17/18 blinks
Turn
to set the control parameter selected
Press
to confirm the setting.
Enter closing direction and blocking posi-
tion:
Closing direction
Direction of rotation causing
the valve to move to the
CLOSED position (view onto
positioner display)
Default: CCL (counterclock-
wise)
Blocking position
Default: 0
Turn
®
Code 34
Press
, Code 34 blinks
Turn
®
Closing direction (CCL counter-
clockwise/CL clockwise)
Press
Turn
®
Code 35
Press
, Code 35 blinks
Turn
®
Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Define the valve closed position:
4
Set switch for
valve closed position
AIR
TO OPEN or AIR TO CLOSE as de-
scribed in section 7.1 on page 56.
4
Set volume restriction as described in
section 7.2 on page 57.
Start initialization:
4
Press INIT key!
The operating mode is changed to auto-
matic mode .
Note:
–
As initialization has not been carried out
completely, the
error code 76
(no emer-
gency mode) and possibly also
error
code 57
(control loop) may appear on
the display.
These alarms do not influence the
positioner’s readiness for operation.
–
If the positioner shows a tendency to os-
cillate in automatic operating mode, the
parameters K
P
and T
V
must be slightly
corrected. Proceed as follows:
Set T
V
to 4 (
Code 18
).
If the positioner still oscillates, the gain
K
P
(
Code 17
) must be decreased until the
positioner shows a stable behavior.
EB 8384-6 EN
67
Start-up – Settings
mm
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...