8, 9
Not used
1
10
CB_UPDATE_EVT
This message is issued when device data are changed
11
CB_SIMULATE
Simulation mode, i.e. values are not derived from the
process
12
CB_DISTURBANCE
Error, see DIAGNOSIS parameter for cause
13
CB_CONTR_ERR
Internal positioner control loop error (must be confirmed
via Class 2 Master). Indicated by LED, automatically reset
provided the control loop monitoring can no longer
determine any error.
14
CB_CONTR_INACT
Positioner is inactive (MODE = out of service)
15
CB_SELFTEST
Device is in selftest mode (MODE = out of service)
16
CB_TOT_VALVE_TRAV
Limit value of total valve travel exceeded
2
17...23
Not used
Device diagnosis messages "Slave Diagnostic Information"
In addition to the standard diagnosis messages, the positioner can provide more messages
as "Ext_Diag_Data". These are encoded bit-wise encoded as well and correspond to the
PROFIBUS PA "Diagnosis" profile parameter.
Bit no.
Name
Description
0
DIA_HW_ELECTR
Hardware error electronics
1
DIA_HW_MECH
Hardware error mechanics
4
DIA_MEM_CHKSUM
Memory checksum error
5
DIA_MEASUREMENT
Measurement error
6
DIA_NOT_INIT
Device not initialized (auto initialization not executed)
7
DIA_INIT_ERR
Auto initialization error
8
DIA_ZERO_ERR
Zero point error (final position)
10
DIA_CONF_INVAL
Configuration incorrect
11
DIA_WARMSTART
Warmstart (restart) completed,
for definition of warmstart, see Profile A
12
DIA_COLDSTART
Coldstart (new start) completed, for definition of coldstart, see Profile A
13
DIA_MAINTAINANCE
Maintenance required
14
DIA_CHARACT
Characteristic invalid
31
EXTENSION_AVAILABLE
More information available
EB 8382-1 EN
41
Summary of Contents for 3785 series
Page 69: ...EB 8382 1 EN 69...
Page 70: ...70 EB 8382 1 EN...
Page 71: ...EB 8382 1 EN 71...
Page 72: ...72 EB 8382 1 EN...
Page 73: ...EB 8382 1 EN 73...
Page 74: ...74 EB 8382 1 EN...
Page 75: ...EB 8382 1 EN 75...
Page 76: ...76 EB 8382 1 EN...
Page 77: ...EB 8382 1 EN 77...
Page 78: ...78 EB 8382 1 EN...
Page 79: ...EB 8382 1 EN 79...