Date last maintenance
VALVE_MAINT_DATE
Indicates the last maintenance date of the field device.
Date of installation
DEVICE_INSTALL_DATE
Indicates the date on which the field device was installed.
Dead band Xtot
DEAD_BAND
Default:
Dead band of the control characteristic
in the range of 0.1 to 10.0 % of the rated travel/nominal angle
0.5 %
Delay time
DELAY_TIME (M)
Default:
Reset criterion for monitoring the active control loop. When the entered delay time
DELAY_TIME is exceeded and the system deviation is not within the limits of the
entered tolerance band TOLERANCE_BAND, a control loop error is reported.
0 to 240 s.
The delay time is determined from the min. transit time during initialization and can
be adapted.
10 s
Derivative-action coefficient KD
SERVO_RATE
Range:
Default:
Gain factor of the derivative element. We recommend increments of 0.02 when
adapting the value. Higher increments cause an increased deceleration before
reaching the reference variable.
0.0 to 1.00
0.12
Description
DESCRIPTOR
Available space for entering texts on the description of the application, stored in the
field device. Length: 32 characters
Device reset
DEVICE_RESET_CMD
States
Default:
Command to reset the device
0 = No action
1 = Reset the device
0
Device status
CHECK_BACK
Message type:
States:
Detailed device information, coded bit-wise encoded which enables several
simultaneous
messages, see also Chapter 9.
A: Dynamic messages; they are automatically reset by readout.
R: Static mess.; they are retained, as long as the event is imminent in the field device
0 = No message
1 = Message active
Diagnosis
DIAGNOSIS
Message type:
States:
Detailed device information, coded bit-wise encoded which enables several
simultaneous messages, see also Chapter 9.
A: Dynamic messages; they are automatically reset by readout.
R: Static messages; they are retained, as long as the event is imminent in the field device.
0: No message
1: Message active
EB 8382-1 EN
51
List of parameters
Summary of Contents for 3785 series
Page 69: ...EB 8382 1 EN 69...
Page 70: ...70 EB 8382 1 EN...
Page 71: ...EB 8382 1 EN 71...
Page 72: ...72 EB 8382 1 EN...
Page 73: ...EB 8382 1 EN 73...
Page 74: ...74 EB 8382 1 EN...
Page 75: ...EB 8382 1 EN 75...
Page 76: ...76 EB 8382 1 EN...
Page 77: ...EB 8382 1 EN 77...
Page 78: ...78 EB 8382 1 EN...
Page 79: ...EB 8382 1 EN 79...