Fail-safe value reference variable
FSAFE_VALUE
Default:
Substitute value for set point (reference variable w or w_rcas) when communication
failure is recognized.
0
Firmware version
SW_REVISION
Firmware version communication/control
Hardware version
HW_REVISION
Hardware version electronics/mechanics
Identification forced venting
IDENT_FORCED_VENTING (M)
States:
Indicates whether the optional forced venting function has been installed.
Read-only parameter (automatically set by the device)
0 = Not installed
1 = Installed
Identification limit switches
IDENT_LIMIT_SWITCHES
(M
)
States:
Default:
Indicates whether the optional inductive limit switch function has been installed (no
automatic identification).
0 = Not installed
1 = Installed
0
Initialization method
INIT_METHOD (M)
States:
Default:
Method of initialization related to the nominal or maximum range.
For initialization in the nominal range, only the range of the manipulated variable
entered under rated travel/nominal angle is considered (e.g. globe valve with
mechanical stop on one side).
When the maximum range is initialized, the maximum permissible range of the
manipulated variable is used (e.g. three-way valve with mechanical stop on both sides).
0 = Initialization related to maximum range
1 = Initialization related to nominal range
0
Local operation enable
LOCAL_OP_EN
States:
Default:
Enables local operation (zero/initialization button) option.
In case of communication failure of more than 30 sec, local operation is enabled.
0 = Disabled
1 = Enabled
1
Message
DEVICE_MESSAGE
Available space for entering texts in the field device.
Length: 32 characters
Mounting position
MOUNTING_POSITION (M)
(Linear actuator)
States:
Default:
An arrow located on the cover plate of the positioner indicates how to attach the
positioner to the actuator.
For direct attachment, the arrow must point toward the actuator, and
for attachment according to NAMUR, the arrow must point away from the actuator.
0 = Arrow pointing away from the actuator
1 = Arrow pointing toward the actuator
1
EB 8382-1 EN
53
List of parameters
Summary of Contents for 3785 series
Page 69: ...EB 8382 1 EN 69...
Page 70: ...70 EB 8382 1 EN...
Page 71: ...EB 8382 1 EN 71...
Page 72: ...72 EB 8382 1 EN...
Page 73: ...EB 8382 1 EN 73...
Page 74: ...74 EB 8382 1 EN...
Page 75: ...EB 8382 1 EN 75...
Page 76: ...76 EB 8382 1 EN...
Page 77: ...EB 8382 1 EN 77...
Page 78: ...78 EB 8382 1 EN...
Page 79: ...EB 8382 1 EN 79...