With a 4 to 20 mA input signal, for exam-
ple, the valve must also move through the
entire range (0 to 100 % ). The starting point
then is 4 mA and the upper range value
20 mA.
In split-range operation, the controller output
signal used to control two control valves is
divided in such a way that these valves
move through their entire travel with half of
the input signal range (e.g. first valve set to
4 to 12 mA, second valve set to 12 to
20 mA). To prevent the two from overlap-
ping, a dead band of ±0.5 mA as in Fig. 13
must be taken into account.
The starting point (zero) is adjusted using
the zero adjustment screw (4), the reference
variable span and, hence, the upper range
value using the pin (2).
4.3 Setting the positioner at the
valve
4
Connect an ammeter to the control signal
input at the terminals 11 (+) and 12 (–).
4
Connect the supply air to the supply input
(supply 9).
4.3.1 Setting the air delivery
(volume restriction Q) and
proportional band XP
1. Close the volume restriction (14) as far
as the required speed of response al-
lows.
You can check the speed of response by
pressing the range spring (6) as far as it
will go.
2. Set the input signal to approximately 50
% of its range. Then, turn the zero adjust-
ment screw (4) until the valve is at ap-
proximately 50 % valve travel.
On setting the Xp restriction, observe the re-
lationship with the supply air pressure as in-
dicated in Fig. 14. The preset value of Xp
should read approximately 3 %.
3. Check the plug stem's tendency to oscil-
lation by pressing the range spring (6)
briefly as far as it will go.
Xp should be set to a value as small as
possible, however, without causing no-
ticeable overshoot.
Note:
Always determine the Xp setting prior to ad-
justing the starting point. Subsequent modifi-
cation displaces the zero point!
The zero can also be shifted by altering the
adjusted supply air pressure.
If necessary, check the zero adjustment un-
der operating conditions of the plant and,
re-adjust, if need be.
EB 8359-2 EN
15
Operation
Zul. Supply Alim.
Xp
[%]
5
4
3
2
1
0
6 bar 3 bar 1.4 bar
90°
0°
180° 270°
270°
90°
180°
0°
360°
Fig. 14 · Setting the XP restriction
Summary of Contents for 4763
Page 22: ...22 EB 8359 2 EN...
Page 23: ...EB 8359 2 EN 23...
Page 24: ...24 EB 8359 2 EN...
Page 25: ...EB 8359 2 EN 25...