Appendix
Code
No.
Parameter
– Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code
3
prior to configuration.
d8
EXPERTplus activation Firmware version 1.5x and higher without function
48* Diagnostic parameters h
h0
Initialization with
reference test
[No], YES, ESC
Initialization with reference test
(the reference graphs for drive signal y steady-state (d1) and drive
signal y hysteresis (d2) (Tests) are recorded during the reference test).
h1
Results of reference test
[No], YES
No No reference test has been performed.
YES The reference graphs for drive signal y steady-state (d1) and
drive signal y hysteresis (d2) (Tests) have been plotted success-
fully.
Read only
h2
Unassigned
h3
Auto reset diAG
[0] to 365 days
After an adjustable time period, the diagnosis data are reset auto-
matically according to the settings in Code 36 - diAG.
Example:
A start-up behavior of the plant which is untypical for the
process is not to be included in the total diagnosis.
h4
Remaining time for
auto reset diAG
Remaining time until the diagnosis data are reset automatically ac-
cording to the settings in Code 48 - h3.
Read only
49* Partial stroke test (PST)/full stroke test (FST) · Application type
A Partial stroke test (PST)
A0
Starting the partial
stroke test
[No], YES, ESC
Operating mode and PST testing mode must be set to MAN.
A1
Time until next
automatic PST
Remaining time [d_h] until the next partial stroke test is performed.
Only applies to PST Auto mode.
Read only
A2
Target PST testing
mode
Auto, [Man], ESC
Activates (PST Auto) or deactivates (PST Man) the scheduled
automatic partial stroke test.
A3
Auto test time
Time [h] between for partial stroke tests (PST)