42
EB 8389 EN
Statistical information
leakage' messages with the selected status
classifications.
If almost all set point deviations during the
short-term monitoring are greater than 1 %
or smaller than –1 %, this may indicated that
the actuator or valve stem is jammed. In this
case, the positioner generates the 'Limit
working range' and 'Connection positioner -
valve' messages with the selected status clas-
sifications.
Diagnosis > Status messages > Extended
−
Limit working range
−
Connection positioner - valve
−
Inner (seat) leakage
4.4.2 Resetting single status
messages
The 'Inner leakage' and 'Limit working
range' messages can be reset by selecting
and executing the command "Reset 'Set
point deviation histogram e'" or "Reset 'Set
point deviation histogram e - Short-term'".
The 'Connection positioner - valve' can be
reset by selecting and executing the com-
mand 'Set point deviation histogram e -
Short-term'".
By selecting and executing the "Reset 'Set
point deviation histogram e'" command, all
diagnostic parameters and measured data
of the histogram and the short-term monitor-
ing are reset.
By selecting and executing the command
"'Reset 'Set point deviation histogram e -
Short-term'", the diagnostic parameters and
measured data in the 'Short-term' folder are
reset.
Operation > Reset
−
Reset 'Set point deviation histogram e'
−
Reset 'Set point deviation histogram e – short-
term'
Summary of Contents for TROVIS 3730-3
Page 6: ...6 EB 8389 EN...
Page 43: ......
Page 57: ......
Page 83: ...EB 8389 EN 83...
Page 130: ...130 EB 8389 EN...