EB 8389 EN
61
Tests
Diagnosis > Status messages > Extended
−
Observing end position
4.8.2 Resetting single status
messages
The 'Observing end position' message and
the measured data of the end position trend
are reset by the command "Reset 'Lower end
position".
If only the reference zero point is to be reset,
select and execute "Reset 'Lower end posi-
tion - Ref. values".
Operation > Reset
−
Reset 'Lower end position trend'
−
Reset 'Lower end position - ref. values'
5 Tests
For reasons of safety, these tests can only be
started when the positioner is in the manual
mode.
The control valve moves through its defined
working range while a test is being per
-
formed. Therefore, it is important to check
before starting a test whether the conditions
(in the plant or process) allow the valve to
move through its working range.
The tests provide a trend showing the current
control valve state, any possible existing
malfunctions and help to pinpoint faults and
to schedule predictive maintenance work.
The following parameters are briefly
changed while the tests are running:
−
Travel/angle range start (Code 8): 0 %
−
Travel/angle range end (Code 9): 100 %
−
Enable travel/angle lower limit (Code
10): Off
−
Enable travel/angle upper limit (Code
11): Off
−
Enable set point cutoff decrease
(Code 14): Off
−
Enable set point cutoff increase
(Code 15): Off
−
Characteristic selection (Code 20): Linear
−
Required transit time OPEN (Code 21):
Variable
−
Required transit time CLOSED (Code 22):
Variable
NOTICE
!