Rotary switch for “Operating modes“

Manual operation: valve closes

0

Manual operation: valve
stationary

+

Manual operation: valve
opens
Control operation deactivated,
frost protection only
DHW heating active, heating
circuit deactivated
Reduced or standby operation

Rated operation

Automatic mode, time-con-
trolled operation

Setting the operating mode

Turn the “Operating mode“ switch to the icon corresponding
with the desired operating mode.
The adjusted operating mode remains active until the rotary
switch is moved to a different position.

Rotary pushbutton for operation

Turning

q

: Select displays, parameters and

function blocks

Pressing

: Confirm adjusted selection or

setting

Rotary switch for “Configuration and parameterization“

COPA

Switch to configuration and
parameter level
Times-of-use for DHW
circulation pump

DHW temperature set point

Day set point
(rated room temperature)
Night set point
(reduced room temperature)

Times-of-use for heating

Controller time: setting the
current time, date and year

INFO

Switch to information level

Retrieving data

INFO

Turn “Configuration and parameterization“ switch to
position

INFO.

Display: time

q

Depending on the configuration of the controller, different
data points are displayed one after the other

Room temperature RS

Outdoor temperature AS

Temperature at flow sensor VS1, heating
circuit/primary heat exchanger circuit

Temperature at return flow sensor RüS

Temperature at flow sensor VS2,
DHW circuit (systems 3…5)

,

Temperature at storage tank sensor
(system code numbers 2…4)
Temperature at return flow sensor
RüS_TW (system code no. 5)

Display set points or limit values of the selected temperature.

Setting the controller time

Turn “Configuration and parameterization“ switch to
position “Controller time“.

Display: time

Activate editing mode for controller time.

blinks.

q

Edit time.
Confirm time.

Display: date (day.month)

Activate editing mode for date.

blinks.

q

Edit date.
Confirm date.

Display: year

Activate editing mode for year.

blinks.

q

Edit year.
Confirm year.

Display: time

Return “Configuration and parameterization“ switch to po-
sition

INFO

.

Display: time

Adjusting times-of-use

Three times-of-use can be set for each day of the week.
If a time-of-use is not needed, the start and stop times for this
time-of-use must be adjusted to identical values.

/

Turn “Configuration and parameterization“ switch

to  position “Times-of-use“ (either for heating or DHW

circulation pump).

Display:

1

q

Select desired period/day for times-of-use:
1 = Monday, 2 = Tuesday ,..., 7 = Sunday, 1-7 = daily
Activate editing mode for period/day.

Display:

1*

,

START

* The display 1 (2, 3) indicates the first (second, third)

time-of-use.

Activate editing mode for start time.

and

blink.

q

Edit start time (steps of 30 minutes).
Confirm start time.

Display:

STOP

q

Edit stop time (steps of 30 minutes).
Confirm stop time.

Display:

2

,

START

Adjust second and third time-of-use similarly.
To adjust times-of-use for certain days, repeat the steps listed in
the gray box in the same order.

Return “Configuration and parameterization“ switch to
position

INFO

.

Display: time

Note!

Do not use the 1-7 menu to check the adjusted times-of-use as
this data point only displays the times-of-use set for Monday.

Setting the temperature set points

/ /

Turn “Configuration and parameterization“

switch to position “Set point“ (either day, night or DHW

temperature).

Display: temperature value

Activate editing mode for temperature set point.

q

Edit temperature set point.
Confirm temperature set point.
Return “Configuration and parameterization“ switch to
position

INFO

.

Display: time

Parameterizing and configuring the controller

The system code number (Anl 1 to Anl 5), functions and parame-
ters are adjusted in configuration and parameter level.
To get to this level, turn “Configuration and parameterization“
switch to position

COPA

.

Changes in COPA level can only be made after the key number
has been entered and confirmed. The key number can be found
in Mounting and Operating Instructions EB 5433 EN.
The controller includes 3 parameter and 3 configuration levels:

PA1:

Parameters for heating circuit

PA2:

Parameters for DHW heating

PA-SYS:

Controller time, public holidays, vacation periods

CO1:

Functions for heating circuit

CO2:

Functions for DHW heating

CO-SYS:

System-wide functions

Note!

Details on how to parameterize and configure the controller can
be found in Mounting and Operating Instructions EB 5433 EN
(section 2). These instructions also contain a complete list of all
parameters and functions.

This quick guide does

not

replace the included Mounting and

Operating Instructions.
All instructions given in the Mounting and Operating Instruc-
tions EB 5433 EN concerning installation, electrical connec-
tion, start-up and operation must be observed.
The controller is ready for operation with the default settings
for temperatures and time schedules. On start-up, the

current

time and date

need to be entered (see “Setting the controller

time“).

Edition February 2003