Rotary switch for “Operating modes“
–
Manual operation: valve closes
0
Manual operation: valve
stationary
+
Manual operation: valve
opens
Control operation deactivated,
frost protection only
DHW heating active, heating
circuit deactivated
Reduced or standby operation
Rated operation
Automatic mode, time-con-
trolled operation
Setting the operating mode
Turn the “Operating mode“ switch to the icon corresponding
with the desired operating mode.
The adjusted operating mode remains active until the rotary
switch is moved to a different position.
Rotary pushbutton for operation
Turning
q
: Select displays, parameters and
function blocks
Pressing
: Confirm adjusted selection or
setting
Rotary switch for “Configuration and parameterization“
COPA
Switch to configuration and
parameter level
Times-of-use for DHW
circulation pump
DHW temperature set point
Day set point
(rated room temperature)
Night set point
(reduced room temperature)
Times-of-use for heating
Controller time: setting the
current time, date and year
INFO
Switch to information level
Retrieving data
INFO
Turn “Configuration and parameterization“ switch to
position
INFO.
Display: time
q
Depending on the configuration of the controller, different
data points are displayed one after the other
Room temperature RS
Outdoor temperature AS
Temperature at flow sensor VS1, heating
circuit/primary heat exchanger circuit
Temperature at return flow sensor RüS
Temperature at flow sensor VS2,
DHW circuit (systems 3…5)
,
Temperature at storage tank sensor
(system code numbers 2…4)
Temperature at return flow sensor
RüS_TW (system code no. 5)
Display set points or limit values of the selected temperature.
Setting the controller time
Turn “Configuration and parameterization“ switch to
position “Controller time“.
Display: time
Activate editing mode for controller time.
blinks.
q
Edit time.
Confirm time.
Display: date (day.month)
Activate editing mode for date.
blinks.
q
Edit date.
Confirm date.
Display: year
Activate editing mode for year.
blinks.
q
Edit year.
Confirm year.
Display: time
Return “Configuration and parameterization“ switch to po-
sition
INFO
.
Display: time
Adjusting times-of-use
Three times-of-use can be set for each day of the week.
If a time-of-use is not needed, the start and stop times for this
time-of-use must be adjusted to identical values.
/
Turn “Configuration and parameterization“ switch
to position “Times-of-use“ (either for heating or DHW
circulation pump).
Display:
1
q
Select desired period/day for times-of-use:
1 = Monday, 2 = Tuesday ,..., 7 = Sunday, 1-7 = daily
Activate editing mode for period/day.
Display:
1*
,
START
* The display 1 (2, 3) indicates the first (second, third)
time-of-use.
Activate editing mode for start time.
and
blink.
q
Edit start time (steps of 30 minutes).
Confirm start time.
Display:
STOP
q
Edit stop time (steps of 30 minutes).
Confirm stop time.
Display:
2
,
START
Adjust second and third time-of-use similarly.
To adjust times-of-use for certain days, repeat the steps listed in
the gray box in the same order.
Return “Configuration and parameterization“ switch to
position
INFO
.
Display: time
Note!
Do not use the 1-7 menu to check the adjusted times-of-use as
this data point only displays the times-of-use set for Monday.
Setting the temperature set points
/ /
Turn “Configuration and parameterization“
switch to position “Set point“ (either day, night or DHW
temperature).
Display: temperature value
Activate editing mode for temperature set point.
q
Edit temperature set point.
Confirm temperature set point.
Return “Configuration and parameterization“ switch to
position
INFO
.
Display: time
Parameterizing and configuring the controller
The system code number (Anl 1 to Anl 5), functions and parame-
ters are adjusted in configuration and parameter level.
To get to this level, turn “Configuration and parameterization“
switch to position
COPA
.
Changes in COPA level can only be made after the key number
has been entered and confirmed. The key number can be found
in Mounting and Operating Instructions EB 5433 EN.
The controller includes 3 parameter and 3 configuration levels:
PA1:
Parameters for heating circuit
PA2:
Parameters for DHW heating
PA-SYS:
Controller time, public holidays, vacation periods
CO1:
Functions for heating circuit
CO2:
Functions for DHW heating
CO-SYS:
System-wide functions
Note!
Details on how to parameterize and configure the controller can
be found in Mounting and Operating Instructions EB 5433 EN
(section 2). These instructions also contain a complete list of all
parameters and functions.
This quick guide does
not
replace the included Mounting and
Operating Instructions.
All instructions given in the Mounting and Operating Instruc-
tions EB 5433 EN concerning installation, electrical connec-
tion, start-up and operation must be observed.
The controller is ready for operation with the default settings
for temperatures and time schedules. On start-up, the
current
time and date
need to be entered (see “Setting the controller
time“).
Edition February 2003
Quick guide KA 5433 EN
Automation
System
TROVIS
5400
Heating
and
District
Heating
Controller
TROVIS
5433
*