13
Appendix
13.1
Configuration levels
Compact version:
Anl. 1.0.0, 1.0.1, 3.5.0 (= all
HC1
)
Standard version:
Anl. 1.0.0, 1.0.1, 1.1.0, 1.1.1, 1.2.0, 2.0.0, 2.1.0, 2.2.0, 3.5.0,
11.0.0, 11.9.0, 11.9.1 (= all
HC1
)
Heating circuit HC1
HC1–
CO1–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
01
Room
temperature
measurement
Not Anl.
1.9.0
1.9.1
OFF
OFF: Room sensor inactive
ON: Temperature reading and input FG1 for
Type 5257-5 Room Panel active
02
Outdoor
temperature
measurement
Not Anl.
1.9.0
1.9.1
ON
OFF: Fixed set point control
ON: Weather-compensated control
03
Return flow
temperature
measurement
Not Anl.
1.9.0
1.9.1
OFF*
ON**
OFF: Function inactive
ON: Return flow temperature measurement and limita-
tion active
1.0
Function block parameter:
Limiting factor / 0.1 to 10.0
*
Anl. 1.0.1, 1.1.1, 1.2.0
** Anl. 1.0.0, 1.1.0, 2.0.0, 2.1.0, 2.2.0, 3.5.0,
11.0.0, 11.9.0, 11.9.1
04
Outdoor
temperature
0–10 V at UI1
All
HC1
OFF
OFF: Function inactive
ON: Outdoor temperature measurement at input UI1;
only when
• HC1–CO1–02 = ON
–20.0 °C
50.0 °C
Function block parameters:
Lower transmission range value, outdoor tempera-
ture / –30.0 to 100.0 °C
Upper transmission range value, outdoor tempera-
ture / –30.0 to 100.0 °C
05
Underfloor
heating
Not Anl.
1.9.0
1.9.1
3.5.0
OFF
OFF: Function inactive
ON: Restriction of adjustment ranges
Function block parameters:
See next page
100
EB 5610 EN
Appendix