DHW–
CO4–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
17
Priority for ex-
ternal demand
Only Anl.
1.6.0
1.6.1
1.6.2
2.0.0
2.1.0
2.2.0
OFF
OFF: Function inactive
ON: Priority for external demand
WARNING!
High external demand lead to exces-
sive charging temperatures in DHW circuits
without control valve.
18
Reserved
19
Scheduled
switchover be-
tween S7 and
S8
Not Anl.
1.9.0
1.9.1
11.0.0
11.9.0
11.9.1
OFF
OFF: Function inactive
ON: Time-controlled sensor switchover; only when
• DHW–CO4–01 = ON and
• DHW–CO4–02 = ON
20
Reserved
21
Release control
circuit 2 at S8
11.0.0
11.2.0
11.9.0
OFF
1
OFF: Function inactive
ON: Control circuit released by binary input S8
Function block parameter:
Switching state of control circuit 2 active / 0, 1
EB 5610 EN
107
Appendix