Functions
WE
Configuration
Room temperature measurement
OFF
HC1–CO1–01 = ON
Outdoor temperature measurement
ON
HC1–CO1–02 = ON
Adaptation
OFF
HC1–CO1–10 = ON
Four-point characteristic
OFF
HC1–CO1–11 = OFF
Parameter
WE
Parameter settings
HC1 day set point
Refer to section 3.1
Note:
If the
Flash adaptation
function is already configured with a small cycle time, the
Adapta-
tion
function should not be configured as well.
6.10
Set point correction using a 0 to 10 V signal
The HC1 set points can be corrected in a linear manner within the range between –8 °C (poten-
tiometer input 1 V) to +8 °C (potentiometer input 9 V). Signals lower than 1 V or greater than
9 V do not have any effect on the HC1 set points.
Note:
The connection of the set point correction using a 0 to 10 V signal (HC1–CO1–15 = ON)
depends on the system selected. Refer to fold-out page.
Function
WE
Configuration
Set point correction using 0 to 10 V
OFF
HC1–CO1–15 = ON
EB 5610 EN
67
Functions of the heating circuit