Functions
WE
Configuration
Storage tank sensor S7
OFF
DHW–CO4–01 = ON
Storage tank sensor S8 (bottom)
OFF
DHW–CO4–02 = ON
Active flow sensor DHW:
Flow sensor DHW
OFF
DHW–CO4–05 = ON
Time-controlled switchover of storage tank sensors:
Scheduled switchover between S7 and S8
OFF
DHW–CO4–19 = ON
Parameters
WE
Parameter settings
Min. adjustable DHW set point
40.0 °C
DHW–PA4–01 / 5.0 to 90.0 °C
Max. adjustable DHW set point
60.0 °C
DHW–PA4–02 / 5.0 to 90.0 °C
Hysteresis
5.0 °C
DHW–PA4–03 / 1.0 to 30.0 °C
Charging temperature boost
10.0 °C
DHW–PA4–04 / 0.0 to 50.0 °C
Max. charging temperature
80.0 °C
DHW–PA4–05 / 20.0 to 130.0 °C
Lag time for storage tank charging pump
90 s
DHW–PA4–06 / 0 bis 600 s
DHW day set point
55.0 °C
Refer to section 3.1
DHW night set point
40.0 °C
72
EB 5610 EN
Functions of the DHW circuit