EB 8384-6S EN
121
EB 8384-6S
121
Operating the positioner
7.10 Reset to default settings
A reset allows the positioner to be reset to the default settings. To reset the positioner, the op-
tions DIAG, STD and DS are available in Code 36. Table 16 lists the reset functions.
Code 36 – DS is usually selected when the valve is mounted in another position or when the
positioner is to be mounted to another valve.
Performing a reset does not necessarily mean the positioner must be re-initialized.
Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1. Turn
until Code 3 appears (reading:
No
).
2. Press , the code number 3 blinks.
3. Turn until
YES
appears.
4. Press
to confirm (reading:
).
Enable configuration
Default: No
Reset start-up parameters:
1. Turn
until Code 36 appears (reading:
••–••–).
2. Press , the code number 36 blinks.
3. Turn until
DIAG/STD/DS
appears.
4. Press
to confirm.
The parameters are reset depending on the
setting made (see Table 16).
Reset
Default: No
Note
Summary of Contents for TROVIS SAFE 3730-6
Page 12: ...12 EB 8384 6S EN...
Page 16: ...16 EB 8384 6S EN...
Page 22: ...22 EB 8384 6S EN...
Page 40: ...40 EB 8384 6S EN...
Page 42: ...42 EB 8384 6S EN...
Page 82: ...82 EB 8384 6S EN...
Page 90: ...90 EB 8384 6S EN...
Page 96: ...96 EB 8384 6S EN...
Page 132: ...132 EB 8384 6S EN...
Page 152: ...152 EB 8384 6S EN...
Page 155: ...EB 8384 6S EN 155...
Page 156: ...156 EB 8384 6S EN...
Page 157: ...EB 8384 6S EN 157...
Page 158: ...158 EB 8384 6S EN...
Page 159: ...EB 8384 6S EN 159...
Page 160: ...160 EB 8384 6S EN...
Page 161: ...EB 8384 6S EN 161...
Page 162: ...162 EB 8384 6S EN...
Page 163: ...EB 8384 6S EN 163...
Page 164: ...164 EB 8384 6S EN...
Page 165: ...EB 8384 6S EN 165...
Page 166: ...166 EB 8384 6S EN...
Page 167: ...EB 8384 6S EN 167...
Page 182: ...182 EB 8384 6S EN...
Page 183: ...EB 8384 6S EN 183...