EB 8384-6S EN
Operating the positioner
Select the initialization mode:
1. Turn
until Code 6 appears.
2. Press , the code number 6 blinks.
3. Turn until
NOM
appears.
4. Press
to confirm the NOM initialization
mode.
Init mode
Default: MAX
Start initialization:
Î
Press INIT key.
Î
After the initialization has been successfully completed:
Check the direction of action (Code 7) and, if necessary, change it.
7.6.3 MAN – Initialization based on a manually selected OPEN
position
Before starting initialization, move the control valve manually to the OPEN position. The
positioner calculates the differential travel/angle from the OPEN and CLOSED positions and
adopts it as the operating range with limits of lower travel/angle range value (Code 8) and
upper travel/angle range value (Code 9).
Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1. Turn
until Code 3 appears (reading:
No
).
2. Press , the code number 3 blinks.
3. Turn until
YES
appears.
4. Press
to confirm (reading:
).
Enable configuration
Default: No
Summary of Contents for TROVIS SAFE 3730-6
Page 12: ...12 EB 8384 6S EN...
Page 16: ...16 EB 8384 6S EN...
Page 22: ...22 EB 8384 6S EN...
Page 40: ...40 EB 8384 6S EN...
Page 42: ...42 EB 8384 6S EN...
Page 82: ...82 EB 8384 6S EN...
Page 90: ...90 EB 8384 6S EN...
Page 96: ...96 EB 8384 6S EN...
Page 132: ...132 EB 8384 6S EN...
Page 152: ...152 EB 8384 6S EN...
Page 155: ...EB 8384 6S EN 155...
Page 156: ...156 EB 8384 6S EN...
Page 157: ...EB 8384 6S EN 157...
Page 158: ...158 EB 8384 6S EN...
Page 159: ...EB 8384 6S EN 159...
Page 160: ...160 EB 8384 6S EN...
Page 161: ...EB 8384 6S EN 161...
Page 162: ...162 EB 8384 6S EN...
Page 163: ...EB 8384 6S EN 163...
Page 164: ...164 EB 8384 6S EN...
Page 165: ...EB 8384 6S EN 165...
Page 166: ...166 EB 8384 6S EN...
Page 167: ...EB 8384 6S EN 167...
Page 182: ...182 EB 8384 6S EN...
Page 183: ...EB 8384 6S EN 183...