14
EB 8389-1S EN
Monitoring
−
Resetting measured data does not cause
the diagnostic parameters and reference
value to be reset as well.
−
The positioner does not need to be re-ini-
tialized after resetting.
Reset measured diagnostic data
Code 36 - Diag
−
Parameters are reset as described in
u
−
Resets diagnostics assessment.
−
Reference values remain unchanged.
−
Status classification and data logs re
-
main saved.
−
The positioner does not need to be re-ini-
tialized after resetting.
−
If the diagnostic data are to be reset at
regular intervals, enter the time in "De-
sired time until ‘Reset measured diagnos-
tic data" (Code 48 - h3). The setting
"00:00:00" causes the resetting at regu-
lar intervals to be deactivated.
Reset start-up parameters
Code 36 - Std
−
Parameters are reset as described in
−
Resets diagnostics assessment.
−
Reference values are deleted.
−
Status classification remains unchanged.
−
Data logs are reset.
−
The positioner must be re-initialized after
resetting.
Reset to default settings
Code 36 - DS
−
Parameters are reset as described in
−
Resets diagnostics assessment.
−
Reference values are deleted.
−
Status classification and data logs are
deleted.
−
The positioner must be re-initialized after
resetting.
Note:
Before mounting the positioner on a
new control valve, perform a reset by
selecting the command 'Reset to de-
fault settings' (Code 36 - DS) and re-
initialize the positioner.