01
PREP
AR
A
TION
11
English
600 or more
600 or more
600 or more
300 or mor
e
300 or more
❋
When 3 sides of the outdoor unit are blocked by the wall
300 or mor
e
1500 or mor
e
600 or more
600 or more
500 or mor
e
500 or mor
e
300 or more
300 or more
❋
When front and rear side of the outdoor unit is towards the wall
❋
The upper part of the outdoor unit and
the air outlet is towards the wall
1500 or more 600 or more 3000 or more
3000 or more
300 or more
❋
When front and rear side of the outdoor unit is towards the wall
• The units must be installed according to distances declared, in order to permit accessibility from each side, either to
guarantee correct operation of maintenance or repairing products.
The unit’s parts must be reachable and removable completely under safety condition (for people or things).
CAUTION
• Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver]
[Rain resistance louver]
• Louver specifications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%
WARNING
Summary of Contents for AC-505CM Series
Page 38: ......