02
INST
ALLA
TION
15
English
Power Cable Specifications
f
The power cable is not supplied with air conditioner.
- Select the power supply cable in accordance with relevant local and national regulations.
- Wire size must comply with the applicable local and national code.
- Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single Phase
Model
Outdoor Units
Input Current (Amperes)
Power Supply
Outdoor Unit
Indoor Unit
Rated
Voltage Range
Outdoor Unit
Indoor
Unit
Total
MCA (A)
MFA (A)
Hz
Volts
Min.
Max.
Cooling Heating
AC012MXQFEC
AC012MNMFEC
50
220-240
198
264
9.0
-
2.5
11.5
11.5
12.7
AC018MXQFEC
AC018MNMFEC
50
220-240
198
264
18.0 -
2.5
20.5
20.5
22.6
AC024MXQFEC
AC024MNMFEC
50
220-240
198
264
18.0 -
2.5
20.5
20.5
22.6
AC030MXQFEC
AC030MNMFEC
50
220-240
198
264
24.0 -
2.5 26.5
26.5
30.0
AC036MXQFEC
AC036MNMFEC
50
220-240
198
264
24.0 -
2.5 26.5
26.5
30.0
AC042MXQFEC
AC042MNMFEC
50
220-240
198
264
32.0
-
2.5 34.5
34.5
40.0
3 Phase
Model
Outdoor Units
Input Current (Amperes)
Power Supply
Outdoor Unit
Indoor Unit
Rated
Voltage Range
Outdoor Unit
Indoor
Unit
Total
MCA (A)
MFA (A)
Hz
Volts
Min.
Max.
Cooling Heating
AC048MXQFGC
AC048MNMFEC
50
380-415
342
457
16.1
-
2.5 18.6
18.6
18.6
AC060MXQFGC
AC060MNMFEC
50
380-415
342
457
16.1
-
2.5 18.6
18.6
18.6
NOTE
1. Voltage
range
- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits
2. Maximum allowable voltage variation between phases is 2%.
3. Wire size & type must comply with the applicable local and national code.
- Wire size : Based on the value of MCA.
- Wire type : Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene
sheathed flexible cord (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66
/ CENELEC H07RN-F)
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5. MCA represents maximum input current.
MFA represents capacity which may accept MCA
❋
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
Summary of Contents for AC-505CM Series