Connecting the Power Terminal
f
Connect the cables to the terminal board using the compressed ring terminal.
f
Cover a solderless ring terminal and a connector part of the power cable and then connect it.
Silver solder
Nominal
dimensions
for cable
[mm
2
(inch
2
)]
Nominal
dimensions
for screw
[mm(inch)]
B
D
d1
E
F
L
d2
t
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Min.
[mm
(inch)]
Min.
[mm
(inch)]
Max.
[mm
(inch)]
Standard
dimension
[mm(inch)]
Allowance
[mm(inch)]
Min.
[mm
(inch)]
4/6
(0.006/
0.009)
4(3/8)
9.5(3/8)
±0.2
(±0.007)
5.6(1/4)
+0.3(+0.011)
-0.2(-0.007)
3.4(1/8)
±0.2
(±0.007)
6
(1/4)
5
(3/16)
20
(3/4)
4.3
(3/16)
+ 0.2(+0.007)
0(0)
0.9
(0.03)
8(3/16)
15(9/16)
9
(3/8)
28.5
(1-1/8)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
10(0.01)
8(3/16)
15(9/16)
±0.2
(±0.007)
7.1(1/4)
+0.3(+0.011)
-0.2(-0.007)
4.5(3/16)
±0.2
(±0.007)
7.9
(5/16)
9
(3/8)
30
(1-3/16)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.15
(0.04)
16(0.02)
8(3/16)
16(10/16)
±0.2
(±0.007)
9(3/8)
+0.3(+0.011)
-0.2(-0.007)
5.8(1/4)
±0.2
(±0.007)
9.5
(5/16)
13
(1/2)
33
(1-5/16)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.45
(0.05)
25(0.03)
8(3/16)
12(1/2)
±0.3
(±0.011)
11.5(7/16)
+0.5(+0.019)
-0.2(-0.007)
7.7(5/16)
±0.2
(±0.007)
11
(3/8)
15
(5/8)
34
(1-3/8)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.7
(0.06)
8(3/16)
16.5(10/16)
13
(1/2)
8.4
(1-3/16)
35(0.05)
8(3/16)
16(10/16)
±0.3
(±0.011)
13.3(1/2)
+0.5(+0.019)
-0.2(-0.007)
9.4(3/8)
±0.2
(±0.007)
12.5
(1/2)
13
(1/2)
38
(1-1/2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.8
(0.07)
8(3/16)
22(7/8)
13
(1/2)
43
(1-
11/16)
8.4
(1-3/16)
50(0.07)
8(3/16)
22(7/8)
±0.3
(±0.011)
13.5(1/2)
+0.5(+0.019)
-0.2(-0.007)
11.4(7/16)
±0.3
(±0.011)
17.5
(11/16)
14
(9/16)
50
(2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
1.8
(0.07)
70(0.10)
8(3/16)
24(1)
±0.4
(±0.015)
17.5(11/16)
+0.5(+0.019)
-0.4(-0.015)
13.3(1/2)
±0.4
(±0.015)
18.5
(3/4)
20
(3/4)
51
(2)
8.4
(1-3/16)
+ 0.4(+0.015)
0(0)
2.0
(0.078)
f
Connect the rated cables only.
f
Connect using a driver which is able to apply the rated torque to the screws.
f
If the terminal is loose, fire may occur caused by arc. If the terminal is connected too firmly, the terminal may be damaged.
Tightening Torque (kgf • cm)
Model
M4
12.0~18.0
Communication : F1, F2
All model
1 phase AC power : 1(L), 2(N), L, N
AC018MXQFEC
AC024MXQFEC
3phase AC power : 1(L), 2(N), L1R, L2(S), L3(T), N
AC048MXQFGC
M5
20.0~30.0
1 phase AC power : 1(L), 2(N), L, N
AC030MXQFEC
AC036MXQFEC
• When connecting cables, you can connect the cables to the electrical part or connect them through the holes
below depending on the spot.
•
Run transmission wiring between the indoor and outdoor units through a conduit to protect against
external forces, and feed the conduit through the wall together with refirgerant piping.
• Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining
and bushing with an electrical insulation such as rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• When the cables are connected through the hole, remove the Plate bottom.
CAUTION