background image

52

Samsung Electronics

4-5  Troubleshooting by symptoms

4-5-1  Communication error after finishing tracking (E202)

1.   Check items
 

1) Is the communication cable short/open?

 

2) Is there a response from the Hydro unit PCB?

2.   Check procedure

No

Yes

Is there a response from the Hydro Unit PCB? 

(LED901 (ORN) in NOT blinking)

No

Yes

In this case, is the

voltage waveform between the lines square 

wave with amplitude over ±0.7V as shown 

in the following picture? 

+0.7V

-0.7V

Good

Bad

Check the communication cable and 

exchange the Hydro Unit PCB

Remove the communication cable

connecting the outdoor unit to indoor unit, 

and measure the signal on LINE 2 of the 

outdoor unit with a scope

Reconnect the cable connecting 

the outdoor unit to the indoor unit 

and restart the unit.

 If the communication still doesn’t work,

 

replace  

the  

comm. kit PCB and 

Check the communication

 

 cable in each PCB

 

 

and replace the PCB

Yes

Is the power/communication

cable connected correctly?

No

Connect the power/communication

cable correctly.

outdoor unit PCB in order of mention.

cf.) If there is no oscillo scope, it can be replaced multimeter instead of osillo scope.

Summary of Contents for AE040JXEDEH

Page 1: ...duct Specifications 3 Disassembly and Reassembly 4 Troubleshooting 5 PCB Diagram 6 Wiring Diagram 7 Reference Sheet Model AE040JXEDEH AE060JXEDEH AE090JXEDEH AE120JXEDEH AE140JXEDEH AE160JXEDEH AE090JXEDGH AE120JXEDGH AE140JXEDGH AE160JXEDGH AE090JNYDEH AE090JNYDGH AE160JNYDEH AE160JNYDGH ...

Page 2: ...used by tracking or short circuit Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches Check the status of the components assembly after repair service The status must be the same as before the repair service 1 2 Precautions related to static electricity and PL The PCB power supply block is susceptible to static electricity There...

Page 3: ... or fire and so on The electric work must be done by service agent or similarly qualified persons according to national wiring regulations and use only rated cable If the capacity of the power cable is insufficient or electric work is not properly completed electric shock or fire may occur Use only rated parts and tools If you don t use the rated parts and tools it can cause trouble with the air c...

Page 4: ... pipe before brazing Brazing with the refrigerant still remaining in the product or pipe may cause poor result and generate harmful gas Furthermore pressure of the refrigerant may increase and cause damage to the leaking part This may lead harmful refrigerant and oil to spurt out which can be dangerous for service personnel Use nitrogen gas to get rid of the oxide forming during brazing Using othe...

Page 5: ...mpressor BLDC electricity Permanent magnet strong magnetic rotor Double rotor compression cylinder Nd Fe B Neodium Iron Boron magnet SAMSUNG s double rotor compressor has the upper and lower rotors designed symmetrically The double rotor in symmetry can remove vibrations caused by the eccentric design of the cylinder 2 rotors balancing the rotary moment Centered symmetry Upper rotor Permanent magn...

Page 6: ...ion of Up to 33 5 Samsung EHS known for its world class efficiency 12kW floor heating system with 4 63 can reduce 33 5 of your running costs as compared to a gas boiler High Performance at Low Temperature Samsung EHS is made up of an inverter compressor optimally operated according to the outdoor temperature offering heating performance of 90 at 10 C and reliable frost protection at 25 C Heat pump...

Page 7: ...tion Max Length Outdoor to m 30 30 50 50 50 50 50 50 50 50 Max Height Between ID OD m 20 20 30 30 30 30 30 30 30 30 Chargeless Length m 15 15 15 15 15 15 15 15 15 15 Refrigerant Type R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A Control Method EEV EEV EEV EEV EEV EEV EEV EEV EEV EEV Factory Charging g 1 400 1 400 1 700 1 900 2 980 2 980 2 980 2 980 2 980 2 980 Power Supply Φ V Hz E 2...

Page 8: ...z 1Ф G 380 4150V 50Hz 3Ф G 380 4150V 50Hz 3Ф Water Pump Type Centrifurugal UPM3 25 7 5 Centrifurugal Stratos 25 1 9 Centrifurugal UPM3 25 7 5 Centrifurugal Stratos 25 1 9 Motor Input W 60 90 60 90 Number of Unit EA 1 1 1 1 Flow Switch Type Magnetic Decreasing Magnetic Decreasing Magnetic Decreasing Magnetic Decreasing Min flow rates LPM 7 1 5 12 1 5 7 1 5 12 1 5 Electric Heater W 4 000 6 000 6 000...

Page 9: ...L Outdoor Unit DB68 05132A 1 Provided for AE040 060 Models ASSY USER MANUAL DB68 05130A 1 Essential Offer Hydro unit ASSY INSTALLATION MANUAL DB68 05131A 1 Pattern sheet DB98 32365A 1 service valve DB96 13833A B 1 wall mounting bracket DB61 04402A 1 ASSY THERMISTOR WATER TANK DB95 05023A 1 SENSOR TEMP MIXING VALVE DB32 00213A 1 Ring band DB81 01572B 1 Sensor holder DB61 40055A 1 Sensor clip DB81 0...

Page 10: ...12 Samsung Electronics Hand Tool sets 3 Disassembly and Reassembly Item Remark Screw Driver Adjustable wrench Screw Driver Nipper Electric Motion Driver L Wrench Torque Lench Latchet Lench ...

Page 11: ...s from it Use Screw Driver 2 Remove pressure sensor by adjustable wrench Use adjustable wrench 230kgf cm 3 Pull the manometer out 4 Push the 2 hooks of cover 5 Pull the bottom of remocon body up 3 1 Hydro Unit AEN160YD AEN080YD Be sure that the power switch is in the OFF and the power source cord shall be unplugged prior to disassembly and reassembly works ...

Page 12: ...bly and Reassembly 14 Samsung Electronics No Parts Procedure Remark 5 Remove the connector from the PCB board 6 Remove the upper case of the controller 7 Remove 5 screws Set a side the drain pan and hydro unit ...

Page 13: ... Parts Procedure Remark 3 Water Pump 1 Remove 4 screws Use Screw Driver 2 Remove the cabi control top 3 Remove the flow switch and connector 4 Remove a pipe from the backup Heater Use adjustable wrench 380kgf cm Use the Torque Wrench when you assemble it ...

Page 14: ...amsung Electronics No Parts Procedure Remark 5 After removing insulation material remove the Thermostat 6 Remove 2 screws Use Screw Driver 7 Remove 2 screws Use Screw Driver 8 Pull the water pump pipes up out AE090JNYSSS AE160JNYSSS ...

Page 15: ... tube of the expansion vessel and the backup heater by adjustable wrench Use adjustable wrench 150kgf cm Use the Torque Wrench when you assemble it 2 Remove 2 screws Use Screw Driver 3 After removing the nut Pull the bracket out 4 Pull the expansion vessel up out 5 Plate Heat Exchanger 1 Remove 4 insulations ...

Page 16: ...mark 2 Remove 4 Thermostats 3 Remove the Thermostat connector on the PCB of the Control box 4 Remove the pipe from the Backup Heater Use adjustable wrench 380kgf cm Use the Torque Wrench when you assemble it 5 Remove 6 screws Use Screw Driver 6 Pull the PHE out of the unit ...

Page 17: ...g Electronics 19 No Parts Procedure Remark 6 Control Box 1 Remoce Thermostats and connectors 2 Remove 3 screws Use Screw Driver 3 Pull the cabi control bottom out by pushing as indicated diretion 1 Phase AESSSJNYDEH 3 Phase AESSSJNYDGH ...

Page 18: ...Disassembly and Reassembly 20 Samsung Electronics No Parts Procedure Remark 7 Backup Heater 1 Remove the Drain Hose 2 After removing 4 screws set a side the backup heater and the unit Use Screw Driver ...

Page 19: ...and remove the three screws on the CABI FRONT RH Use type screw driver 2 CABI TOP 1 Unscrew and remove the nine screws on each side of the CABI TOP Use type screw driver 3 CABI INSTALL FRONT 1 Unscrew and remove the screw on the CABI INSTALL FRONT Use type screw driver AEX100EDS AEX125EDS AEX140EDS AEX160EDS 3 2 Outdoor Unit ...

Page 20: ...Disassembly and Reassembly 22 Samsung Electronics No Parts Procedure Remark 4 GUARD COND 1 Pull the sensor from Guard Cond 2 Unscrew and remove the four screws on the GUARD COND Use type screw driver ...

Page 21: ...ly and Reassembly Samsung Electronics 23 No Parts Procedure Remark 5 CABI BACK RH 1 Pull the sensor from the CABI BACK RH 2 Unscrew and remove the nine screws on each side the CABI BACK RH Use type screw driver ...

Page 22: ...Disassembly and Reassembly 24 Samsung Electronics No Parts Procedure Remark 6 CABI INSTALL BACK 1 Unscrew and remove the 8 screws on the CABI FRONT LF Use type screw driver ...

Page 23: ...Disassembly and Reassembly Samsung Electronics 25 No Parts Procedure Remark ...

Page 24: ...Disassembly and Reassembly 26 Samsung Electronics No Parts Procedure Remark 7 FAN 1 Turn the two nuts as shown in the picture and remove them Use adjustable wrench ...

Page 25: ...y and Reassembly Samsung Electronics 27 No Parts Procedure Remark 8 MOTOR 1 Remove the fan 2 Unscrew and remove the eight motor screws Use type screw driver 3 Disconnect the motor wire from the Ass y Control Out ...

Page 26: ...Disassembly and Reassembly 28 Samsung Electronics No Parts Procedure Remark 9 BRACKET MOTOR 1 Unscrew and remove the two screws on the BRACKET MOTOR Use type screw driver ...

Page 27: ...msung Electronics 29 No Parts Procedure Remark 10 CONTROL OUT 1 Disconnect the six connectors form the ASSY Control OUT 2 Unscrew and remove the three screws on the CONTROL OUT Use type screw driver 3 Separate the ASSY CONTROL OUT ...

Page 28: ...AY VALVE 1 Purge the coolant first 2 Unscrew and remove the four screws on the SERVICE VALVE Use type screw driver 3 Separate the pipe from the Entrance Exit using a welder When removing the compressor heat exchanger and pipe purge the completely and remove the pipe with a welding flame ...

Page 29: ...1 No Parts Procedure Remark 12 COMPRESSOR 1 Unscrew and remove the nut on the COVER TERMINAL Use adjustable wrench 2 Separate the compressor wire 3 Separate the COMPRESSOR FELT SOUND 4 As shown in the picture unscrew and bottom Use Adjustable Wrench ...

Page 30: ...Disassembly and Reassembly 32 Samsung Electronics No Parts Procedure Remark 13 ASSY COND OUT 1 Unscrew remove the two screws on each side of the ASSY COND OUT Use type screw driver ...

Page 31: ... 1 Common Work 1 Loosen 1 fixing screw of the Cover Control and detach the Cover Control 2 Loosen fixing screws and detach the Cabinet Upper 3 Loosen 1 screw fixed to assemble Control Box with Cabinet Side RH 4 Loosen 6 fixing screws and detach the Cabinet Side RH AEX060EDEHA ...

Page 32: ...Disassembly and Reassembly 34 Samsung Electronics No Parts Procedure Remark 5 Loosen 2 screws fixed on the Guide Condenser 6 Loosen fixing screws of the Cabinet Front ...

Page 33: ... screw is left handed 2 Detach the Fan Propeller 3 Loosen 4 fixing screws to detach the Motor 4 Disconnect the wire between Ass y Control Out and Motor 5 Loosen 2 fixing screws and detach the Bracket Motor 3 Ass y Control Out 1 Detach several connectors from the Ass y Control Out 2 Detach several connectors from the PCB of Ass y Control Out 3 Pull up the Ass y Control Out ...

Page 34: ...th welding torch 4 Detach the Heat Exchanger Before you disassemble the pipes and Condenser be sure that there should be no refrigerant remained in the unit 1 Loosen fixing screw CCW and detach the Heat Exchanger 5 Compressor 1 Loosen the fixing nut and detach the Compressor Lead Wire 2 Disassemble the Felt Comp Sound 3 Loosen the 3 bolts at the bottom of Compressor like the picture on the right s...

Page 35: ...on error 1 min Check the communication connection between indoor and outdoor units Check the power line and communication cable connection status Operation Off Communication error Communication error between indoor outdoor INV MAIN MICOM 1 min Check MAIN MICOM Check INVERTER MICOM Communication error Outdoor temperature sensor error Check sensor connection status Check sensor location Check sensor...

Page 36: ...Inverter DC LINK voltage sensor error Check the input power connection Check the status of RY21 and R200 in the INVERTER PCB Operation Off Outdoor unit protection control error Inverter OTP error Check EEPROM DATA Check the normal operation of PCB Operation Off Outdoor unit protection control error AC ZERO CROSSING SIGNAL OUT error Check the input power status Operation Off Outdoor unit protection...

Page 37: ...the voltage waveform between the lines square wave with amplitude over 0 7V as shown in the following picture 0 7V 0 7V Good Bad Check the communication cable and replace the indoor unit PCB Remove the communication cable connecting the outdoor unit to indoor unit and measure the signal on LINE 2 of the outdoor unit with a scope Reconnect the cable connecting the outdoor unit to the indoor unit an...

Page 38: ...isplay Symptom EEPROM circuit failure Failure EEPROM component failure EEPROM circuit parts missing damaged soldering failure 4 2 2 EEPROM circuit failure No Yes Are the EEPROM circuit components in good conditions missing components damage soldering failure Replace the PCB if the restart fails ...

Page 39: ...ication failure between EEPROM and MICOM Outdoor unit display Yes Are there any problems such as short or dewetting between EEPROM PIN If you restart after reentering model options and power reset does the error occur again Replace PCB Yes No Normal operation No 1 How to check Check the location of EEPROM by referring to the schematic diagram Replace PCB 4 3 Hydro Unit ...

Page 40: ...ed indoor unit No The thermistor needs to be replaced No Re start after put the connetor in the PBA Yes Does wired remocon room thermistor connector come out of the PBA Is the resistance value Deviated from the temp table significantly Yes 1 How to check After putting out the thermistor from the PBA Measure its resistance value B W two terminal Re start after replacing PBA Temperature C Resistance...

Page 41: ...door unit No Re start after put the connetor in the PBA Yes 1 How to check After putting out the thermistor from the PBA Measure its resistance value B W two terminal The thermistor needs to be replaced No Is the resistance value Deviated from the temp table significantly Yes Re start after replacing PBA Temperature C Resistance KΩ 70 60 50 40 30 21 10 0 10 2 2 3 0 4 2 5 8 8 3 12 1 18 0 27 3 43 0 ...

Page 42: ...ed indoor unit No Re start after put the connetor in the PBA Yes 1 How to check After putting out the thermistor from the PBA Measure its resistance value B W two terminal The thermistor needs to be replaced No Is the resistance value Deviated from the temp table significantly Yes Re start after replacing PBA Temperature C Resistance KΩ 70 60 50 40 30 20 10 0 43 59 82 115 166 242 362 553 Does wate...

Page 43: ...after put the connetor in the PBA Yes 1 How to check Flow S W needs to be replaced Is it OPEN Yes Check water pump operates properly Does flow S W connector come out of the PBA Yes After putting out the connector F S from the PBA Measure its status is OPEN or SHORT Re start after replacing PBA No Check water flow rate Is it proper Yes E911 Water pump ON Flow S W off Water pump ON Flow S W off NOT ...

Page 44: ...he connetor in the PBA Yes 1 How to check Flow S W needs to be replaced Yes Is it short No Measure status of PBA is OPEN or SHORT Does flow S W connector come out of the PBA Yes After putting out the connector F S from the PBA Measure its status is OPEN or SHORT No Is it short Yes Water pump OFF Flow S W on E912 No Yes Yes Does the water flow PBA needs to be replaced Does any extra water pump inst...

Page 45: ...ature sensor disconnected from the connector in PCB Restart the system after replacing the PCB Restart the system after connecting to the PCB connector Temperature sensor failure replace Remove the temperature sensor connector from the PCB and measure the resistance between two terminals 4 3 7 Hydro unit temperature sensor open short Current temperature C Resistance kΩ 60 59 16 55 69 44 50 81 92 4...

Page 46: ...voltage waveform between the lines square wave with amplitude over 0 7V as shown in the following picture 0 7V 0 7V Good Bad Check the communication cable and replace the Hydro unit unit PCB Remove the communication cable connecting the outdoor unit to Hydro unit unit and measure the signal on LINE 2 of the outdoor unit with a scope Reconnect the cable connecting the outdoor unit to the Hydro unit...

Page 47: ...it 1s digit C 8 Outlet water sensor MONO 8 10s digit 1s digit C 9 Cond sensor 9 10s digit 1s digit C 10 Current A 10s digit 1s digit First decimal A 11 Fan RPM B 1000s digit 100s digit 10s digit rpm 12 Target discharge temperature C 100s digit 10s digit 1s digit C 13 EEV D 1000s digit 100s digit 10s digit step 14 Protective control E 0 Cooling 1 Heating Protective control 0 No protective control 1...

Page 48: ...AIN OLP Sensor Error Check OLP sensor Open Short E320 9 MAIN Detection of Outdoor Freezing when Comp Stop Check Outdoor Cond E403 10 MAIN Protection of Outdoor Overload when Comp Stop Check Comp when it start E404 11 MAIN Discharge temperature of a compressor in an outdoor unit is overheated E416 12 MAIN Outdoor EEV Open error Check EEV E419 13 MAIN Miss wiring error at 3Phase power source line On...

Page 49: ...AIN INVERTER PFC Overload Error Check Outdoor Inverter PBA E484 31 MAIN Input current sensor error E485 32 MAIN INVERTER IPM is over heated Check Outdoor Inverter PBA E500 33 MAIN GAS Leak error Check indoor and outdoor unit model E554 34 MAIN Water inlet temperature sensor error Check Water inlet sensor E901 35 MAIN Water outlet temperature sensor error Check Water outlet sensor E903 36 MAIN Refr...

Page 50: ... Bad Check the communication cable and exchange the Hydro Unit PCB Remove the communication cable connecting the outdoor unit to indoor unit and measure the signal on LINE 2 of the outdoor unit with a scope Reconnect the cable connecting the outdoor unit to the indoor unit and restart the unit If the communication still doesn t work replace the comm kit PCB and Check the communication cable in eac...

Page 51: ...ly between MAIN PBA and INVERTER PBA 2 Is the power cable connected correctly 2 Check procedure Does the communication error occur Yes No Normal operation Is the communication power cable connected properly between MAIN PBA and INVERTER PBA Yes Connect the connector right position Exchange MAIN PBA INVERTER PBA in order of mention No CN39 in MAIN PBA CN31 in INVERTER PBA 4 5 ...

Page 52: ...ck the sensor cable and connector Does the value of resistance satisfy the each temperature condition Yes No Exchange the temperature sensor Power on Yes Is the wire of sensor broken or is there any poor contact Yes No the temperature sensor CN43 in MAIN PBA Pin no Temp sensor Error code 1 2 Outdoor E221 3 4 Condenser E231 5 6 Discharge E251 7 8 OLP E320 Error code for each temperature sensor 0 5 ...

Page 53: ... broken Is each resistance of FAN cable housing normal Resistance of FAN cable housing at the normal temperature 10 C 30 C wire pin number Resistance Remark RED BLACK 1 3 over 1MΩ 300V motor power WHITE BLACK 4 3 1KΩ 2KΩ 15V control power YELLOW BLACK 5 3 200KΩ 300KΩ control BLUE BLACK 6 3 10KΩ 50KΩ pulse ORANGE BLACK 7 3 10KΩ 50KΩ reverse Mount each Fan housing to PCB socket and turn on the power...

Page 54: ...F Yes Yes No No Cont Exchange INVERTER PCB Exchange the FAN motor Is the Pin voltage 6 3 of CN90 and 91 changed high 4 5V and low 0 1V in case of making manual rotation slowly Is the Pin voltage 7 3 of CN90 and 91 low 0 1V in normal rotation Exchange INVERTER PCB 4 8 Troubleshooting ...

Page 55: ...operation Is the value of resistance between each phase for compressor smaller than 2Ω Yes No 3 Is the resistance normal between each phase for compressor Exchange the compressor Is the value of resistance megaΩ between compressor and outdoor unit body Yes No Yes No Check the wire of compressor Compressor starting error E461 Compressor wire missing error E467 U V V W W U Exchange the compressor Is...

Page 56: ...obstacle Yes No 3 Does the fan of outdoor unit work normally Does the compressor work normal Yes No Are the service valves fully opened Yes No Open the service valves Primary current trip error E462 Over current trip PFC over current error E463 Exchange the compressor 4 Is there any obstacle around indoor and outdoor unit Is the indoor unit installed well according to installation manual Reinstall...

Page 57: ...he obstacle Yes No 3 Is the connection of compressor correctly Are the service valves fully opened Yes No Open the service valves 4 Is there any obstacle around indoor and outdoor unit Is the indoor unit installed well according to installation manual Reinstall after remove the obstacle Is the wire of compressor connected correctly Yes No Check the wire of compressor Is the value of resistance bet...

Page 58: ...nt error E464 cont Yes No Are the position and measured value of temperature sensor normal reposition the sensor reposition the sensor cont Is the value of resistance megaΩ between compressor and outdoor unit body Yes No Exchange the compressor Exchange INVERTER PCB ...

Page 59: ... power connected correctly 2 Check procedure Is the power cable connected correctly Yes No Connect the power cable Yes No Check whether a fuse has blown Yes No Exchange the fuse Is the reactor connected correctly Check the connection of reactor Does the error occur frequently Yes No Exchange INVERTER PCB Check the input power AC 230V 15 ...

Page 60: ...e error occur Yes No Normal operation Yes No Are the service valves fully opened Yes No Open the service valves Is the evaporator sensor of indoor unit connected correctly Yes No Connect the sensor s connector Yes No Charge refrigerant Is the value of resistance between each phase for compressor smaller than 2Ω Exchange the compressor U V V W W U Is refrigerant charged Exchange INVERTER PCB ...

Page 61: ... the Check the outdoor temperature E441 Cooling operation is not available since the outdoor air temperature is lower than 15 C E465 Compressor over load error Compressor is overloaded Please check same as E461 and check compressor when it starts E468 Current sensor error Exchange INVERTER PBA E471 Outdoor EEPROM error EEPROM date is wrong Exchange EEPROM or MAIN PBA This error don t occur in EMF ...

Page 62: ...sistance value of 4 WAY valve coil Go to the next page 4 WAY valve main body error Attach the sensor correctly Over shortage of the refrigerant Connect the connecter correctly 4 WAY valve coil error Exchange the outdoor PCB No Yes Yes Yes OK Yes No No No NG No Is much frost in the indoor heat exchanger Does the 4 WAY valve operate normally Is the outdoor air sensor and outdoor heat exchanger attac...

Page 63: ...ge of DC300V apply to the connector of outdoor fan during the operation of outdoor unit The over shortage of refrigerant t Capacity Load estimation error Connect the connector Outdoor fan error Check the motor wire Exchange the out PCB EEV coil error Connect the connector Is much frost in the heat exchanger Is much frost in the heat exchanger Outdoor PCB error EEV main body error No No NG No Yes N...

Page 64: ...No Is the outdoor unit power supply N R N S N T 220Vac Yes Check connection of the outdoor unit terminal block No Is the outdoor unit power voltage L N 220Vac Yes Check the connection wires and connectors of the indoor and outdoor units No Is the indoor unit power supply voltage L N 220Vac Yes Exchange the wired remote controller No Does the air conditioner operate when pressing ON OFF button of t...

Page 65: ...nected correctly CN39 MAIN PCB CN31 INVERTER PCB Is the FUSE on INVERTER PCB blown Check and correct the wire or socket connection Check Fuses listed blow 3 FUSES in EMI PCB 1 FUSE in MAIN PCB No Is there miss connection of power and communication wire between indoor and outdoor Correct the cable wiring between indoor and outdoor Check F1 F2 communication line wiring CN50 MAIN PCB Check and correc...

Page 66: ...Samsung Electronics 69 5 PCB Diagram 5 1 Hydro unit This Document can not be used without Samsung s authorization 22 23 21 20 19 18 17 16 15 14 13 12 11 10 8 7 6 5 4 3 2 1 ...

Page 67: ... TB C F1 F2 DC12V GND F3 F4 DAPC 2009 6P BLK 10 CNS041 FLOW SWITCH YW396 02V BLU 11 CNS042 WATER TANK SMW250 02 YEL 12 CNS046 SMART GRID SMW250 02 RED 13 CNS062 EEV SMW250 05 BLU 14 CNS044 ROOM SMW250 02 WHT 15 CNS045 MIXING SENSOR SMW250 02 BLU 16 CNS047 HEATER SMW250 02 BLK 17 CNS043 HEATER EVA OUT EVA IN WATER OUT WATER IN SMW250 10 WHT 18 CNS201 SUB_LED SMW200 07 WHT 19 CNS2 FR_CONTROL AKZ350 ...

Page 68: ...ctronics 71 5 2 Outdoor Unit MAIN PCB AE090 120 140 160JXEDEH EU AE090 120 140 160JXEDGH EU This Document can not be used without Samsung s authorization 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 23 21 22 20 19 ...

Page 69: ... CN001 EVA IN SMW250 02 WHT 9 CN803 EEV1 SMW250 05 BLU 10 CN407 HIGH_P S W SMW250 02 BLU 11 CN802 EEV4 SMW250 06 BLU 12 CN306 DOWNLOAD YDW200 20P BLK 13 CN403 OUT TEMP COND DISQ OLP SMW250 08 WHT 14 CN703 BASE HEATER YW396 03AV BLU 15 CN702 4WAY 1 YW396 03AV YEL 16 CN701 HOTGAS YW396 03AV RED 17 CN101 POWER YW396 03AV WHT 18 CN806 EEPROM B7P MQ WHT 19 CN304 DRED DAPC 2009 6P BLK 20 CN501 MODE SELE...

Page 70: ...on Description 1 CN71 COMP 42819 3213 BLK 2 REACTOR A2 REACTOR_A YTR250 3 REACTOR B2 REACTOR_B YTR250 4 REACTOR A1 REACTOR_A YTR250 5 REACTOR B1 REACTOR_B YTR250 6 L AC POWER BRN WIRE 7 N AC POWER SKY BLU WIRE 8 CN31 MAIN COMM SMW250 06 WHT 9 CN91 BLDC FAN2 YW396 06V WHT 10 C22 DOWNLOADER SMW200 10 RED 11 CN90 BLDC FAN1 YW396 06V WHT 12 CN21 DAC ENCODER SMW200 08 WHT ...

Page 71: ...MP 42819 3213 BLK 2 REACTOR A1 REACTOR_A YTR250 3 REACTOR B1 REACTOR_B YTR250 4 L AC POWER BRN WIRE 5 N AC POWER SKY BLU WIRE 6 CN91 BLDC FAN2 YW396 06V WHT 7 CN90 BLDC FAN1 YW396 06V WHT 8 CN31 MAIN COMM SMW250 06 WHT 9 C22 DOWNLOADER SMW200 10 RED 10 CN21 DAC ENCODER SMW200 08 WHT 11 REACTOR B2 REACTOR_B YTR250 12 REACTOR A2 REACTOR_A YTR250 1 12 11 10 9 8 7 6 1 5 4 3 2 ...

Page 72: ...cal Function Description 1 CN800 COMP 42819 3213 BLK 2 CN600 REACTOR HLW1005 02 BLK 3 R R IN YTR250 4 S S IN YTR250 5 T T IN YTR250 6 CN100 POWER YW396 03AV WHT 7 CN91 BLDC FAN2 YW396 06V WHT 8 CN90 BLDC FAN1 YW396 06V WHT 9 CN31 MAIN COMM SMW250 06 WHT 10 CN22 DOWNLOADER SMW200 10 RED 11 CN21 DAC ENCODER SMW200 08 WHT 6 5 4 3 2 1 7 8 9 10 11 ...

Page 73: ...ent can not be used without Samsung s authorization 7 5 6 4 3 2 1 No Local Function Description 1 L1 POWER OT 048 2 EARTH EARTH YEL GRN WIRE 3 1 L POWER BRN WIRE 4 L POWER BRN WIRE 5 N POWER SKY BLU WIRE 6 2 N POWER SKY BLU WIRE 7 N1 POWER OT 048 8 CN01 AC POWER YW396 03AV WHT ...

Page 74: ...ion No Local Function Description 1 EARTH EARTH YEL GRN WIRE 2 R IN POWER WHT WIRE 3 S IN POWER BRN WIRE 4 T IN POWER BLK WIRE 5 N IN POWER SKY BLU WIRE 6 N INV POWER SKY BLU WIRE 7 T INV POWER BRN WIRE 8 T OUT POWER BLK WIRE 9 S OUT POWER BRN WIRE 10 R OUT POWER WHT WIRE 11 CN01 POWER YW396 03AV WHT 6 7 8 9 10 11 1 4 5 3 2 ...

Page 75: ...tronics SUB HEATER PCB AE090 120 140 160JXEDEH EU AE090 120 140 160JXEDGH EU This Document can not be used without Samsung s authorization No Local Function Description 1 CN02 POWER YW396 03AV YEL 2 CN03 HEATER YW396 03AV WHT 2 1 ...

Page 76: ...gram Samsung Electronics 79 INVERTER PCB AE040 060JXEDEH EU This Document can not be used without Samsung s authorization 1 2 3 4 5 6 9 11 7 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 10 8 ...

Page 77: ...R250 13 CN206 SUB PBA SMW200 10 WHT 14 CN204 DRED SMW250 05 WHT 15 CN051 REACTOR YTR250 16 CN052 REACTOR YTR250 17 CN150 SMPS POWER YW396 03 BLK 18 CN151 HIGH PRESS S W YW396 02V WHT 19 CN002 POWER YTR250 20 CN003 EARTH GP881205 21 CN001 POWER YTR250 22 CN241 HOT GAS YW396 03AV RED 23 CN030 4WAY YW396 03AV WHT 24 CN242 BASE HEATER YW396 03AV BLU 25 CN301 COMM YW396 02V RED 26 CN205 SUB PBA SMW200 ...

Page 78: ...518 DC POWER SMW200 05 BLK 2 CN502 MAIN SUB SIGNAL SMW200 10 BLK 3 CN511 DC 12V YW396 02V BLU 4 CN01 SOLUTION_COMM AKZ350 GRN 5 CN501 MAIN SUB SIGNAL SMW200 10 BLU SUB DISPLAY PCB AE040 060JXEDEH EU 1 2 3 4 5 This Document can not be used without Samsung s authorization ...

Page 79: ...82 Samsung Electronics 6 Wiring Diagram 6 1 Hydro unit 6 1 1 3Phase Model This Document can not be used without Samsung s authorization ...

Page 80: ...Samsung Electronics 83 This Document can not be used without Samsung s authorization 6 1 2 1Phase Model ...

Page 81: ...84 Samsung Electronics 6 2 Outdoor Unit 3Phase AE090 100 120 140JXEDGH This Document can not be used without Samsung s authorization ...

Page 82: ...Wiring Diagram Samsung Electronics 85 1Phase AE090 100 120 140JXEDEH This Document can not be used without Samsung s authorization ...

Page 83: ...Wiring Diagram 86 Samsung Electronics 1Phase AE040 060JXEDEH This Document can not be used without Samsung s authorization ...

Page 84: ...NASA X Outdoor unit NASA Capacity 40 WATT 100 120 WATT 100 60 WATT 100 140 WATT 100 90 WATT 100 160 WATT 100 120 WATT 100 140 WATT 100 160 WATT 100 Mode H HEAT PUMP R410a Series version D STANDRAD STANDARDTANK Feature 1 Y Indoor Unit HYDRO UNIT Wall mounted E Outdoor Unit SINGLE X HYDRO UNIT TANK all in one Power E E 220 240V 50Hz 1Ø G G 380 415V 50Hz 3Ф N J D E H Y ...

Page 85: ...sensor T_dis Discharge temp sensor T_eva in Eva In temp sensor T_eva out Eva Out temp sensor T_condout Condout temp sensor PHE Plate heat exchanger HV Heater vessel EV Expansion vessel This Document can not be used without Samsung s authorization The Direction of this product 4WAY V V connection is heating default Heating 4Way valve Off Cooling 4Way valve ON Normal A C EHS SPLIT AESSSJXEDSH ...

Page 86: ... Electronics 89 7 2 FSV data check and update using S Net Pro2 To check the EHS HE HT FSV data the Update button must be selected FSV value has been updated double click each cell can set the value of the FSV ...

Page 87: ...90 Samsung Electronics 7 3 EHS FSV Values Import and Export The User can now export the existing FSV values into an XML file and update later onto a new unit the saved values ...

Page 88: ...Samsung Electronics 91 Export Values The existing FSV values can be exported by click on the Export button ...

Page 89: ...amsung Electronics FSV Import The FSV values can be imported by the click on the import button The user is prompted to browse and select the XML file for update on the EHS unit selected in the dropdown menu ...

Page 90: ...Samsung Electronics 93 ...

Page 91: ...icable International and or domestic law Samsung Electronics Co Ltd Feb 2015 Printed in Korea Code No AC 00100E_1 GSPN Global Service Partner Network Area Web Site Eurpoe CIS Mideast Africa gspn1 samsungcsportal com Asia gspn2 samsungcsportal com North Latin America gspn3 samsungcsportal com China china samsungportal com ...

Reviews: