General Overview
Samsung Electronics
11
2-2 Model names of Indoor/Outdoor Unit
2-2-1 Indoor Unitt
Model
Capacity
2.2 kW
2.8 kW
3.6 kW
5.6 kW
7.1 kW
9 kW
16 kW
200 Liter 260 Liter
Hydro unit
Slim duct
MSP duct
RAC(Not
include EEV)
Console
TANK
INTEGRATED
HYDRO UNIT
1. Make sure to use an indoor unit that is compatible with EHS TDM PLUS.
2. Indoor units can be connected within the range indicated in following table.
3. If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the
indoor unit may decrease.
4. Total capacity of the connected indoor units can be allowed from 50% to 100% of the total outdoor unit capacity.
0.5 x Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor unit ≤ 1.0 x Σ (Outdoor unit capacity)
5. You can connect maximum 7 indoor units to the outdoor unit.
Maximum quantity of connectable indoor unit is set to 7 since outdoor unit only support up to 7 communication address. Indoor unit
address can be assigned from 0~7.