19
English
Installation Pr
oc
edur
e
Air vent of the fan coil unit
300 mm or less
1000 to 1500 mm
20 mm or
more
Full thread bolt hanger
550 mm or less
Horizontal drain pipe
(transverse pipe) More than 1/100 slope
Flexible hose
Ceiling
Horizontal connection
Fan coil unit
Fan coil unit
Fan coil unit
200 mm
or less
Flexible hose
20 mm or less
30 ° or less
• Connect
the
flexible
hose horizontally.
• Make sure that the maximum
axis gap does not exceed 20 mm.
(Upward axis gap is prohibited.)
• Make
sure
that
the
maximum bending angle
does not exceed 30°.
(Upward slope is prohibited.)
Concentrated drainage
Full thread bolt hanger
Connect to the main drain pipe.
Air vent of the fan coil unit
1000 to 1500 mm
Main air vent (must be installed)
20 mm or more
550 mm or less
Centralized horizontal drain pipe
(more than 1/100 slope)
1
If 3 or more fan coil units are installed, install the main air vent at the front of the farthest fan coil unit from the main
drain pipe.
2
If the slope of the centralized horizontal drain pipe is less than 1/100, be sure to install an air vent at the top of each
fan coil unit to prevent water from flowing back to the unit.