31
English
Installation Pr
oc
edur
e
Setting the fan coil unit installation option
(suitable for the condition of each installation
location)
1
Make sure that the power is supplied to the fan coil
unit.
• If the fan coil unit is not plugged in, it must include
a power supply.
1(L)
F2
2(N)
F1
Fan coil unit
2
Make sure that the panel or display is connected to the
fan coil unit so that it can receive options
3
Set an address for each fan coil unit using the remote
control, according to your air conditioning system plan.
• The fan coil unit addresses are set to 020010-
100001-200000-300000 by default.
• The SEG20 option, individual control with remote
control, allows you to control multiple fan coil units
individually by using the remote control.
4
Set the fan coil unit installation options using the
remote control.
Installation options for the 02 series
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
Use of external temperature sensor
/ Minimizing fan operation when
thermostat is off
Use of central
control
-
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Use of drain pump
Use of hot water heater
-
-
Dew removal operation in
Wind-Free mode /
Auto Evaporator Drying
fan mode / Auto fan smart
comfortable mode
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
Use of external
control
External control output /
External heater output / Cooling
operation output / Cooling
output by external equipment
S-Plasma ion
Buzzer control
Maximum filter usage time
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control with
remote control
Heating setting compensation
-
-
-
• Slim
1
way
– Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to "Use + 3 minute delay."
– If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to
2 (1000 hours).
• If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
• The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don't need to set the SEG5 option
additionally. Note that even if the central control system is not connected, no errors occur. If you want a specific fan
coil unit not to be controlled by the central control system, set the SEG option of that fan coil unit to 0 (Disuse).
• The external heater output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of AIM-B14)