Step 13 Performing the test operation
1
Before turning on the product, measure resistances
between the power terminals (single phase: L, N)
and the earthing of the fan coil unit using a DC 500V
insulation resistance meter.
•
Ɵ˵ʪ͔ʪɇϑЇθʪʒЭɇ̷Їʪϑ͔Їϑϩɵʪɇϩ̷ʪɇϑϩߤߡđץࢋ
CAUTION
• Never measure resistance for the communication
terminal. Failure to do so may damage the
communication circuit.
• Use a general circuit tester to check the
communication terminal for short circuit.
2
Before turning on the product, check the voltage of
the power source (L, N).
<ELB>
N
220 to 240 V
L
3
After completing the installation, check the following
to ensure that the fan coil unit operates normally:
• Strength of the installation site
• Water
leakage
• Power and electric wiring connections
• Heat-resistant insulation of the pipes
• Drainage
• Connections to the auxiliary circuit breaker,
earthing status
• Normal operation in each operation mode
4
After finishing the test run, refer to the user manual
and explain the following to the customer:
• Starting and stopping the fan coil unit
• Using the operation modes and the functions
• Cleaning the fan coil unit and replacing the filter
CAUTION
• For the test run, be sure to operate each fan coil unit
separately to secure S-NET data.
• After installation, test run, and delivery, tell the user to
store the user manual and this installation manual in
a safe place.
CAUTION
Operating precautions
• Be sure to operate heat sources (chiller, boiler) after
starting the fan coil unit.
• Be sure to stop the fan coil unit after stopping heat
sources (chiller, boiler).
• When heat sources (chiller, boiler) are not used for
more than 4 hours in Cool mode, stop the water
circulation.
• If the water circulation cannot be stopped, operate the
fan at low speed.
– If cold water flows while the fan of the fan coil unit
is stopped, condensation may develop on the fan
coil unit (main unit, motor, grill, etc.), shortening
the product life.
• Do not use the product in hot and humid places
(relative humidity 80% or more).
– Water falling from the product may cause fire or
property damage.
• In winter, operate the water pump continuously for
water circulation.
• When a season ends or when the product is not used
for a long time, completely drain water from the entire
system.
– Failure to do so may cause the pipes to freeze and
burst, leading to property damage.