background image

34

English

Extr

a Pr
oc

edur
es

Extra Procedures

Extra procedures

Pumping down refrigerant

  WARNING

 

After installing the product, be sure to perform leak 

tests on the piping connections. After pumping down 

refrigerant to inspect or relocate the outdoor unit, 

be sure to stop the compressor and then remove the 

connected pipes.

 

Do not operate the compressor while a valve is 

open due to refrigerant leakage from a pipe or an 

unconnected or incorrectly connected pipe. Failure 

to do so may cause air to flow into the compressor 

and too a high pressure to develop inside the 

refrigerant circuit, leading to an explosion or 

product malfunction.

Pump-down is an operation intended to collect all the 

system refrigerant in the outdoor unit.
This operation must be carried out before disconnecting 

the refrigerant pipe in order to avoid refrigerant loss to 

the atmosphere.

Turn the system on in cooling with fan operating at 

high velocity and then let the compressor run for more 

than 5 minutes. (Compressor will immediately start, 

provided 3 minutes have elapsed since the last stop.)

Release the valve caps on High and Low pressure side.

Use L-wrench to close the valve on the high pressure 

side.

After approximately 2 minute, close the valve on the 

low pressure side.

Stop operation of the air conditioner by pressing the 

(Power) button on the indoor unit or remote control.

Disconnect the pipes.

Relocating the indoor and outdoor units

Pump down refrigerant. See 

Pumping down 

refrigerant

 on page 34. 

Remove the power cord. 

Disconnect the assembly cable from the indoor and 

outdoor units. 

Remove the flare nuts connecting the indoor units and 

the pipes. At this time, cover the pipes of the indoor 

unit and the other pipes using a cap or vinyl plug to 

avoid foreign material entering. 

Disconnect the pipes connected to the outdoor units. 

At this time, cover the valve of the outdoor units and 

the other pipes using a cap or vinyl plug to avoid 

foreign material entering. 

Note: Make sure you do not bend the connection pipes in 
the middle and store together with the cables. 

Move the indoor and outdoor units to a new location. 

Remove the mounting plate for the indoor unit and 

move it to a new location. 

 

  NOTE

 

Before relocating the units, be sure to thoroughly read 

Recovery

 on page 6.

 

When recharging R-32 refrigerant after it has been 

completely removed, be sure to charge only the factory 

refrigerant amount.

 

When vacuuming the product, be sure to proceed for 

at least 1 hour.

 

Be sure to use an electronic balance when measuring 

the amount of refrigerant, and make sure that only the 

specified amount is charged.

  CAUTION

 

If more than the amount of refrigerant specified on the 

label is charged, a fire may occur when the refrigerant 

leaks.

 
 
 
 

A(Gas)

B(Liquid)

Summary of Contents for AJ NCJ2EG Series

Page 1: ...nditioner Installation manual AJ NCJ2EG Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference DB68 07383...

Page 2: ...utdoor unit in place 10 Step 4 Connecting the power cables communication cable and controllers 11 Step 5 Optional Extending the power cable 16 Step 6 Connecting the refrigerant pipe 18 Step 7 Optional...

Page 3: ...is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply In orderto prevent electric shoc...

Page 4: ...egulations with harnesses ladders scaffolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer While in installation or relocation of t...

Page 5: ...to store the units in a place without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater The service engineers shall not use any...

Page 6: ...ed Cylinders shall be equipped with pressure relief valves and shut off valves in a proper order The recovery system shall operate normally according to the specified instructions and shall be suitabl...

Page 7: ...installed in an open space that is always ventilated The local gas regulations shall be observed For installation inside a building this applies eitherto indoor or outdoor units installed inside a mi...

Page 8: ...at the seaside make sure that it is not directly exposed to sea breeze If you cannot find an adequate place free from direct sea breeze construct a protection wall or a protective fence Install the o...

Page 9: ...e 3000 or more 300 or more 600 or more 600 or more 1500 or more 300 or more 1500 or more 600 or more 600 or more 300 or more 600 or more 600 or more 600 or more 300 or more 300 or more 300 or more 500...

Page 10: ...caused byvibration When installing the unit at a height or in a location exposed to strong winds fix the unit securely to a support i e a wall or a ground 1 Position the outdoor unit so that the airfl...

Page 11: ...utdoor unit The outdoor to indoor power cable between the outdoor unit and the indoor unit The communication cable between the outdoor unit and the indoor unit CAUTION During installation make first t...

Page 12: ...Specifications for local wiring power supply cord and branch wiring are in compliance with local cord NOTE 1 Power Supply cords of parts of appliances for outdoor use shall not be lighterthan polychl...

Page 13: ...tach the transmitter main PCB to the case then connect F1 F2 lines R1 R2 lines which are upper controller communication cables and DC 12V power cables to the interface module referring to the figure o...

Page 14: ...edure English Installation Procedure 1 ON DIP 2 3 4 R1 R2 F1 F2 F1 F2 1 L 2 N 1 L 2 N F1 F2 DC12V Blue Transmitter MAIN PCB Outdoorunit HUB PCB Terminal Block in the outdoorunit AJ040NCJ2EG AJ050NCJ2E...

Page 15: ...ich is able to apply the rated torque to the screws If the terminal is loose fire may occur caused by arc If the terminal is connected too firmly the terminal may be damaged Tightening torque kgf cm M...

Page 16: ...ding the power cable 1 Prepare the following tools Tools Spec Shape Crimping pliers MH 14 Connection sleeve mm 20x 6 5 HxOD Insulation tape Width19 mm Contraction tube mm 70x 8 0 LxOD 2 As shown in th...

Page 17: ...mpleted wrap it with the insulation tape to finish CAUTION Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinfor...

Page 18: ...mandatory to consider eitherthe table 1 ortaking into consideration the local law regarding the minimum living space of the premises Minimum installation height of indoor unit is 0 6 m for floor mount...

Page 19: ...piping extension Maximum allowable piping length 15 m When connecting the pipes make sure that surrounding objects do not interfere with or contact them to prevent refrigerant leakage due to physical...

Page 20: ...s loaded with sufficient R 32 refrigerant Do not vent R 32 into atmosphere it is a fluorinated greenhouse gas covered by Kyoto Protocol with a Global Warming Potential GWP 675 You should purge the air...

Page 21: ...tallation insulation of the cables hose and piping and fixing of the indoor unit to the installation plate you must check that there are no gas leaks To check for gas leaks on the Then using a leak de...

Page 22: ...ce every12 months according to regulation n 517 2014 This activity has to be covered by qualified personnel only In case situation above 5 tCO2e or more of R 32 installer or recognized person which ha...

Page 23: ...When recharging refrigerant from the refrigerant cylinderto the equipment follow the instructions below Before recharging check whetherthe cylinder has a siphon or not There are two ways to recharge...

Page 24: ...green yellow wire 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 Install a green yellow coloured earthing wire If the earthing wire is too short connect...

Page 25: ...are finished successfully the LED indications change as shown in the following table and the outdoor unit stops A B RED GRN RED GRN YEL b If automatic address setting or pipe installation fails the L...

Page 26: ...or reset the outdoor unit NOTE Key information K1 Pipe Checking Operation K3 Reset The LED indications are the same as in the automatic address setting mode Setting Option AR Low Temp button High Temp...

Page 27: ...ion button with the direction of remote control for set CAUTION SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG1 SEG7 as ON status and SEG13 SEG19 as OFF status Set the each option separa...

Page 28: ...utton to enter SEG9 value 2 Press button to enter SEG10 value Step 6 Press button to be changed to HEAT mode in the ON status 1 Press button to enter SEG11 value 2 Press button to enter SEG12value Ste...

Page 29: ...Step10 Press button to be changed to FAN mode in OFF status 1 Press button to enter SEG21 value 2 Press button to enter SEG22 value Step11 Press button to be changed to HEAT mode in the OFF status 1...

Page 30: ...runit Indicationand details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A sin...

Page 31: ...on and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 2 0 0 0 No use 0 1 Use Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explan...

Page 32: ...is started check the temperature difference between the air inlet and outlet of the indoor unit If the temperature difference is largerthan the value given in the following table the operation is norm...

Page 33: ...or unit display turns on again Standby mode operation When all indoor units are turned off the air conditioner recognizes it and enters the standby mode The product power consumption in the standby mo...

Page 34: ...air conditioner by pressing the Power button on the indoor unit or remote control 6 Disconnect the pipes Relocating the indoorand outdoorunits 1 Pump down refrigerant See Pumping down refrigerant on...

Page 35: ...t sheet leaks turn the axis back by half tighten the stopping box then check the leakage again If there is no leakage any more tighten the axis entirely Closing the stop valve 1 Remove the cap 2 Turn...

Page 36: ...Error Code Explanation Remark Red Green Yellow E201 The number of indoor unit mismatched E202 Communication errer between the outdoor and indoor unit E203 Outdoor communication error between main mico...

Page 37: ...or Fan Error E461 Inverter compressor starting failure 5 times E462 Compressortrip by input current control mode PFC over current E463 Compressortrip by OLP temperature control mode E464 DC Peak syste...

Page 38: ......

Reviews: