36
English
Appendix
Troubleshooting
The table below list the self-diagnostic routines. For some of error, you must contact
an authorized service center.
If an error occurs during the operation, it is displayed on the outdoor unit HUB PCB.
‐
The error codes in the list are for reference only. They are not displayed on the
outdoor unit HUB PCB.
‐
If an error occurs while the product is operating normally, all LEDs of the A part
are turned off.
‐
If an error occurs during the installation, the green LED of the A part turns on. Take
corrective actions, and then see Setting the indoor unit addresses automatically on
page 24 and proceed with setting the indoor unit addresses again.
‐
: On, : Off, : Blinking
1
ON
DIP
2
3
4
Display (B part)
Error
Code
Explanation
Remark
Red
Green Yellow
E201
The number of indoor unit mismatched
E202
Communication errer between the outdoor and
indoor unit
E203
Outdoor communication error between main
micom and inverter micom
E206
Outdoor communication error beween main
micom and hub micom
E221
Outside temperature sensor error (Short/Open)
E237
Condenser temperature sensor error (Short/Open)
E251
Compressor Discharge temperature sensor error
(Short/Open)
E320
Compressor OLP sensor error (Short/Open)
E330
EvaIn1 Sensor error (Short/Open)
E331
EvaIn2 Sensor error (Short/Open)
E332
EvaIn3 Sensor error (Short/Open)
E333
EvaIn4 Sensor error (Short/Open)
E334
EvaIn5 Sensor error (Short/Open)
E335
EvaOut1 Sensor error (Short/Open)
E336
EvaOut2 Sensor error (Short/Open)
E337
EvaOut3 Sensor error (Short/Open)
E338
EvaOut4 Sensor error (Short/Open)
E339
EvaOut5 Sensor error (Short/Open)
Appendix
Appendix
Dip Switch
LED
(RED, GRN / RED,GRN,YEL)
K3
K1
A
B