2. Specification
DVM S2 (208~230V)
Model Name
AM288BXVGFH/AA
AM312BXVGFH/AA
AM336BXVGFH/AA
Outdoor unit module 1
AM096BXVGFH/AA
AM096BXVGFH/AA
AM096BXVGFH/AA
Outdoor unit module 2
AM192BXVGFH/AA
AM216BXVGFH/AA
AM240BXVGFH/AA
Outdoor unit module 3
-
-
-
Wiring
Connections
TransmissionCable
Min.
Remark
-
F1, F2
F1, F2
F1, F2
Power supply intake
-
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
Refrigerant
4)
Type
-
R410A
R410A
R410A
FactoryCharging
lbs (kg)
17.6 x 1 + 27.6 x 1
(8.0 x 1 + 12.5 x 1)
17.6 x 1 + 34.2 x 1
(8.0 x 1 + 15.5 x 1)
17.6 x 1 + 34.2 x 1
(8.0 x 1 + 15.5 x 1)
Sound
5)
SoundPressure
Cooling
dB(A)
64.0
64.8
66.5
Heating
dB(A)
6)
SoundPower
dB(A)
86.0
86.0
87.2
External
Dimension
Net Weight
lbs (kg)
553 x 1 + 822 x 1
(251 x 1 + 373 x 1)
553 x 1 + 842 x 1
(251 x 1 + 382 x 1)
553 x 1 + 842 x 1
(251 x 1 + 382 x 1)
ShippingWeight
lbs (kg)
591 x 1 + 880 x 1
(268 x 1 + 399 x 1)
591 x 1 + 900 x 1
(268 x 1 + 408 x 1)
591 x 1 + 900 x 1
(268 x 1 + 408 x 1)
Net Dimensions
(WxHxD)
㎜
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
inch
(51 x 66-3/4 x 30-1/8) x 1 +
(73-1/4 x 66-3/4 x 30-1/8) x 1
(51 x 66-3/4 x 30-1/8) x 1 +
(73-1/4 x 66-3/4 x 30-1/8) x 1
(51 x 66-3/4 x 30-1/8) x 1 +
(73-1/4 x 66-3/4 x 30-1/8) x 1
Shipping Dimensions(WxHxD)
㎜
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
inch
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
(75-15/16 x 74-5/16 x 32-11/16) x 1
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
(75-15/16 x 74-5/16 x 32-11/16) x 1
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
(75-15/16 x 74-5/16 x 32-11/16) x 1
7)
Operating
Temp. Range
Cooling
℉
(
℃)
5 ~ 122 (-15 ~ 50)
5 ~ 122 (-15 ~ 50)
5 ~ 122 (-15 ~ 50)
Heating
℉
(
℃)
-22 ~ 75 (-30 ~ 24)
-22 ~ 75 (-30 ~ 24)
-22 ~ 75 (-30 ~ 24)
66.8
67.6
68.5
AWG
18
18
18
NOTE
• Specification
may
be
subject to
change
without prior notice.
1)
Nominal
capacities
are
based
on
(Equivalent
refrigerant
piping
:
25ft,
Level
differences
:
0ft);
- Cooling
:
Indoor
temperature
80
℉
DB, 67
℉
WB
/
Outdoor
temperature
95
℉
DB, 75
℉
WB
- Heating
:
Indoor
temperature
70
℉
DB,
60
℉
WB
/
Outdoor
temperature
47
℉
DB, 43
℉
WB
2)
The standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
Combination ratio of up
to 184% is allowed depending on operation mode, minimum operation ratio and connected indoor unit models.
DVM Pro 2 design software supports
designing over 130% based on system design.
Refer to the “Design Procedure & Combination Ratio” section of this document for details
3) If outdoor unit is located in a higher position than indoor unit, level difference is 361ft or under.
(If the level difference is higher than 164ft, the PDM kit should be installed)
*PDM kit: Pressure Drop Modulation kit
4)
These
products
contain
R410A
which
is
fluorinated
greenhouse
gas.
5)
Sound
pressure
was
acquired
in
a
dead
room.
Thus
actual
noise
level
may be
different
depending
on
the
installation
conditions.
6)
Sound
power level
is
an
absolute
value
that a
sound
source
generates.
Sound
pressure
level
is
a
relative
value,
depending
on
the
distance
and
acoustic
environment.
Sound
values are
obtained
in
an anechoic room.
Sound
values
of
multi
comvination
are
theoretical
values
based
on
sound
results
of
individual
installed
units.
7)
Cooling
operation
is
possible
at
-
15℃(5℉)
or
higher
if
satisfied
following
conditions.
(If
the
outdoor
temperature
below
-
5℃(23℉),
wind(snow)
protection
duct
must
be
installed
on
the
suction
side
of
the
heat
exchanger
and
at least
50%capacity
of
the
connected
indoor
units
must
be
operated.)
However,
if
the
outdoor
unit
is
installed
below
the
indoor
unit,
cooling operation is
possible only at
-
5℃(23℉)
or
higher.
•
For more information regarding capacity correction, please refer to capacity tables available at www.SamsungHVAC.com/downloads.