1
3
. Installation
Base construction and installation of the DVM Hydro unit HT
Anchor specification
Dimension of the Hydro unit
HE
b
c
a
m
Unit: mm (inch)
Size Diameter of drill
bit (a)
Anchor length (b) Sleeve length (c)
Insert depth
Fastening torque
M10
(3/8”) 14 mm (0.6 inch) 75 mm (3.0 inch) 40 mm (1.6 inch) 50 mm (2.0 inch) 30 N·m (22.1 lbf·ft)
340 (13 .4)
333 (13 .1)
330 (13 .
0)
16 (0 .
6)
599 (23 .6)
365
(14 .
4)
626 (24 .
6)
27 (1 .
1)
120 (47 .
2)
67 (23 .
6)
Water outlet pipe
Communication
cable Gas pipe
Liquid pipe
Power cable
Water inlet pipe
518 (20 .4)
73 (28 .7)
65 (25 .6)
90 (35 .4)
Model of the DVM Hydro unit
AM036CNBD
✴✴
AM048CNBD
✴✴
AM096CNBD
✴✴
AM144CNBD
✴✴
Refrigerant
side
Liquid side
connection part
3/8” (ø9.52)
3/8” (ø9.52)
1/2” (ø12.7)
Gas side connection
part
5/8” (ø15.88)
7/8” (ø22.23)
1-1/8” (ø28.58)
Water side connection part
NPT 1" (25A)
NPT 1" (25A)
NPT 1-1/4" (32A)