42
English
Ins
tallation par
t
Installation Procedure
Setting an indoor unit address (MAIN/RMC)
1
Check whether power is supplied or not.
– When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2
Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
3
Assign an indoor unit address by wireless remote control.
The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
Mode
Setting Main address
100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of an
indoor unit
Indication
and Details
Indication DetailsI Indication Details Indication
Details Indication
Details
Indication
Details
Indication
Details
0
A
0
No
Main
address
0~9
100-digit
0~9
10-digit
0~9
A unit
digit
1
Main
address
setting
mode
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
-
Setting RMC address
-
Group channel(*16)
Group address
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
No RMC
address
RMC1
0~F
RMC2
0~F
1
RMC
address
setting
mode
CAUTION
•
When A~F is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
•
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option
value of SEG5~6.
•
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of
SEG11~12.
•
You cannot set SEG11 and SEG12 as F value at the same time.
DVM_BORACAY_IB_DB68-06415A-00_EN.indb 42
2016-08-31 오후 2:13:30