background image

18

Installation Procedure

English

Installation Pr

oc

edur

e

• Apply 

following 

equation.

n

Coef×35.6×L

k

×i

k

॥࣍

  )  < 

10% of input voltage[V]

k=1

 1000×A

k

• Calculation

 

– Installing with 1 sort wire.

2.5 [mm

2

]

2.5 [mm

2

]

-2.2 [V]

-2.0 [V]

220 [V]

-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2 [V]

208.8 [V] :  

Applicable

Within 198V 

to 242V

·······  2.5 [mm

2

]  ·······

 

– Installing with 2 different sort wire.

4.0 [mm

2

]

4.0 [mm

2

]

-1.4 [V]

-1.2 [V]

220 [V]

-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5 [V]

209.5 [V] :  

Applicable

Within 198V 

to 242V

·······  2.5 [mm

2

]  ·······

  CAUTION

•  Select the power cable in accordance with relevant 

local and national.

•  Wire size must comply with local and national code.
•  You should connect the power cable into the power 

cable terminal and fasten it with a clamp.

•  The unbalanced power must be maintained within 10% 

of supply rating among whole indoor units.

•  If the power is unbalanced greatly, it may shorten 

the life of the condenser. If the unbalanced power is 
exceeded over 10% of supply rating, the indoor unit is 
protected, stopped and the error mode indicates

•  Connect the power cable to the auxiliary circuit breaker. 

An all pole disconnection from the power supply must be 

̈͝ʀͱθΧͱθɇϩʪʒ̈͝ϩ˵ʪ˙̈уʪʒӥθ̈͝˝्࣍ߤ͔͔࣎ࢋ

•  You must keep the cable in a protection tube.
•  Maximum length of power cables are decided within 

10% of power drop. If it exceeds, you must consider 
another power supplying method.

•  The circuit breaker(MCCB, ELB) should be considered 

more capacity if many indoor units are connected from 
one breaker.

•  Use round pressure terminal for connections to the 

power terminal block.

•  For wiring, use the designated power cable and 

connect it firmly, then secure to prevent outside 
pressure being exerted on the terminal board.

•  Use an appropriate screwdriver for tightening the 

terminal screws. A screwdriver with a small head will 
strip the head and make proper tightening impossible.

•  Over-tightening the terminal screws may break them.

Step 13  Optional: Extending the power 

cable

Prepare the following tools.

Tools

Spec

Shape

Crimping pliers

MH-14

Connection sleeve 

(mm)

20xØ6.5 

(HxOD)

Insulation tape

Width 19 

mm

Contraction tube 

(mm)

70xØ8.0 

(LxOD)

As shown in the figure, peel off the shields from the 
rubber and wire of the power cable.
•  Peel off 20 mm of cable shields from the pre-

installed tube.

Power cable

(Unit: mm)

20

20

20

60

120

180

Pre-installed 

tube for the 

power cable

20

20

20

60

120

180

  CAUTION

•  For information about the power cable specifications for 

indoor and outdoor units, refer to the installation manual.

•  After peeling off cable wires from the pre-installed 

tube, insert a contraction tube.

Summary of Contents for AM TN4 KH Series

Page 1: ...Airconditioner Installation manual AM TN4 KH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference...

Page 2: ...nit 9 Step 6 Cutting and flaring the pipes 9 Step 7 Connecting the assembly pipes to the refrigerant pipes 10 Step 8 Performing the gas leak test 11 Step 9 Insulating the refrigerant pipes 11 Step10 I...

Page 3: ...designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the powersupply In orde...

Page 4: ...c lines Always verify that the cut off and protection switches are suitably dimensioned Verify that the airconditioneris connected to the power supply in accordance with the instructions provided in t...

Page 5: ...unit must be installed such that it is beyond public access and is not touchable by users Rigid wall without vibration Where it is not exposed to direct sunshine Where the airfilter can be removed an...

Page 6: ...nit mm The sub duct hole is not applicable to the Wind Free models A A A 9 Model AM170TN4DKH A mm 372 B mm 222 C mm 338 Net dimension W D H mm 840 x 840 x 372 Liquid pipe connection mm 9 52 Gas pipe c...

Page 7: ...of breakage You must hold the hanger plate on the corner and carry the indoor unit Step 3 Optional Insulating the bodyof the indoorunit If you install a cassette type indoor unit on the ceiling when t...

Page 8: ...sure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of each attached suspension bolt If the length of the suspension bolt is more...

Page 9: ...E To prevent dirt orforeign objects from getting into the pipes during installation do not remove the pinch pipe completely until you are ready to connect the piping Step 6 Cutting and flaring the pip...

Page 10: ...e refrigerant tube to protect the condensate water on the outside of the pipe falling onto the floor and to improve the efficiency of the unit 3 Cut off any excess foam insulation 4 Make sure that the...

Page 11: ...7 2000 requiring the use of sheaths insulation without using CFC and HCFC gases for health and the environment 2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulatio...

Page 12: ...ding construction condition Ceilings frequently exposed to moisture and cooling are not covered For example pipes installed at a corridor of a dormitory and studio or near an exit that opens and close...

Page 13: ...re Drain hose Ceiling Do not give the hose an upward gradient beyond the connection port This will cause waterto flow backwards when the unit is stopped resulting in waterleaks Under gradient Ceiling...

Page 14: ...rubber cap on the connection part of a flexible hose of the indoor unit and firmly tighten it with a band to prevent leakage c Check the leak test at the part where the adhesive forthe flexible hose a...

Page 15: ...rop under10 The auxiliary circuit breaker ELCB MCCB ELB should be considered more capacity if many indoor units are connected from one breaker Connect F3 F4 for communication to the communication cabl...

Page 16: ...ew mm B D d1 E F L d2 t Standard dimension mm Allowance mm Standard dimension mm Allowance mm Standard dimension mm Allowance mm Min Min Max Standard dimension mm Allowance mm Min 1 5 4 6 6 0 2 3 4 0...

Page 17: ...mula k 9 AA9 NOTE X The capacity of ELB MCCB Rated currents Model Rating current A AM170TN4DKH 0 83 2 Decide the power cable specification and maximum length within10 voltage drop among indoor units n...

Page 18: ...be Maximum length of power cables are decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker MCCB ELB should be considered more capacity if...

Page 19: ...d be 8 0 Compression dimension After compressing it pull both sides of the wire to make sure it is firmly pressed Compress it 4 times 5 mm Method 1 Compress it 4 times 5 mm Method 2 5 Wrap it with the...

Page 20: ...ies from the remote control and then insert them again b While holding down the High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are ente...

Page 21: ...Press the Mode button Cool and On appear on the remote control display 3 Set the SEG4 and SEG5 values a Set the SEG4 value by pressing the Low Fan button repeatedly until the value you want to set ap...

Page 22: ...remote control display SEG9 b Set the SEG10 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fa...

Page 23: ...r SEG15 12 Press the Mode button Cool and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by pressing the Low Fan button repeatedly until the value you...

Page 24: ...e remote control display SEG21 b Set the SEG22 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High...

Page 25: ...tton on the remote control twice Make sure that this command is received by the indoor unit When it is successfully received you can hear a short sound from the indoor unit If the command is not recei...

Page 26: ...ion see the S NET Pro 2 Help From SEG13 to SEG18 is for setting MCU address A A k MCU S4NEK3N MCU S1NEK1N Option No foran indoorunit address 0AXXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5...

Page 27: ...ion value forthe SEG11 or SEG12 You cannot set the SEG11 or SEG12 to F value at the same time If the indoor unit is connected to the MCU you can set the SEG15 18 Ex If you want to set the indoorunit t...

Page 28: ...n to 0 it is automatically set to 2 the drain pump is used with 3 minute delay If you set the Maximum filter usage time SEG18 option to a value otherthan 2 and 6 it is automatically set to 2 1000 hour...

Page 29: ...g 2 4 Disuse Use Cooling 2 1 RPM compensation 5 Use Use Cooling 2 4 Use 10min 1 6 Disuse Use Heating Cooling 2 1 Use 7 Use Use Heating Cooling 2 8 Disuse Use CoolingUltra LowFan 2 2 Highceiling KIT 4w...

Page 30: ...pedunit duringoilreturn defrostmode SettingtheMDSKitinstallationoption Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSetti...

Page 31: ...the indoor unit heat exchanger Since the watervapor might be condensed on the indoor unit which may fall into a living space use this function to get rid of the water vapor out of the indoor unit by o...

Page 32: ...s Indication Details 0 5 0 Follow product option 0 0 C 0 0 C 0 1 C 1 0 5 C 1 0 5 C 1 1 5 C 1 UseAuto Change Over forHR only 2 1 C 2 1 C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 2 Use Cooling on...

Page 33: ...minutes C 6 0 C No delay D 6 0 C 10 minutes E 6 0 C 20 minutes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE Forcing FAN Operation forHeating and Cooling Indication and Details Indicati...

Page 34: ...tting 02 series SEG9 1 Setting 05 series SEG18 0 The hot water heater is turned on at the same time as the heating thermostat is on and turned off when the heating thermostat is off k k k compensation...

Page 35: ...ption type 0 to F Tens position value 0 to 9 Units position value 0 to 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1 SEG2 SEG3...

Page 36: ...Earth conductor connection Correct operation follow the steps below Afterfinishing the installation of the airconditioner you should explain the following to the user Referto appropriate pages in the...

Page 37: ...Otheroutdoorunit sensorerrorthat is not on the above list for2 minutes E101 X X 2 Communication errorreceived from the outdoorunit E102 3 3 miniute tracking erroron outdoorunit E202 4 Communication e...

Page 38: ...ion control E413 13 Compressordown due to lowpressure sensorprevention control_1 E410 14 Simultaneous opening of cooling heating MCU SOLvalve 1st detection E180 15 Simultaneous opening of cooling heat...

Page 39: ...39 English Appendix MEMO...

Page 40: ......

Reviews: