19
English
Instal
lation
1. Pour water into the condensate pan.
2. Make sure that draining is done properly by checking end of the drain pipe.
3. If water leakage occurs, make sure the indoor unit is level. Also verify the drain pipe is installed with a downward slope away
from the indoor unit.
CAUTION
•
After connecting the drain pipe to the indoor unit, you must perform leakage test. If the drain test has
not done properly, water may get into the indoor and cause property damage.
•
Empty the condensation water in the drain pan before any repair/maintenance service.
Water leakage test
Drain pipe insulation
Fix securely without any gap.
Indoor unit
CAUTION
•
You must insulate drain pipes.
•
Make sure to prevent any gap between the insulation on drain pipe elbows.
•
Make sure that insulation is overlapped.