41
English
Instal
lation
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode change
Heating → Cooling
(When setting SEG3)
Time required for
mode change
Compensation option for Long pipe or
height diff erence between indoor units
Use of MTFC
(Multi Tenant
Function controller)
-
Indication
and Details
Indication Details Indication
Details
Indication Details Indication
Details
Indication Details
-
1
0
1.8 °F (1 °C)
0
5 min.
0
Use default value
0
Disable
MTFC
1
2.7 °F (1.5 °C)
1
7 min.
1
1) Height difference
(*1)
is more
than 30 m or
2) Distance
(*2)
is longer than 110 m
2
3.6 °F (2 °C)
2
9 min.
3
4.5 °F (2.5 °C)
3
11 min.
4
5.4 °F (3 °C)
4
13 min.
2
1) Height difference
(*1)
is 15 ~ 30 m or
2) Distance
(*2)
is 50 ~ 110 m
2
Enable
MTFC
5
6.3 °F (3.5 °C)
5
15 min.
6
7.2 °F (4 °C)
6
20 min.
7
8.1 °F (4.5 °C)
7
30 min.
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
-
-
-
-
-
Control variables when using heater
Indication
and Details
-
-
-
-
-
Indication
Details
Set temp. for heater On/Off
Delay time for heater On
0
At the same time as thermo on
No delay
1
At the same time as thermo on
10 minutes
2
At the same time as thermo on
20 minutes
3
2.7 °F (1.5 °C)
No delay
4
2.7 °F (1.5 °C)
10 minutes
5
2.7 °F (1.5 °C)
20 minutes
6
5.4 °F (3 °C)
No delay
7
DEFAULT - 5.4 °F (3 °C)
10 minutes
8
5.4 °F (3 °C)
20 minutes
9
8.1 °F (4.5 °C)
No delay
A
8.1 °F (4.5 °C)
10 minutes
B
8.1 °F (4.5 °C)
20 minutes
C
10.8 °F (6.0 °C)
No delay
D
10.8 °F (6.0 °C)
10 minutes
E
10.8 °F (6.0 °C)
20 minutes
(*1)
Height difference : The difference of the height between the corresponding indoor unit and the indoor unit installed at
the lowest place.
For example, When the indoor unit is installed 131.2 ft (40 m) higher than the indoor unit installed at
the lowest place, select the option “1”.
(*2)
Distance : The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and
the pipe length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 328 ft (100 m) and the corresponding indoor unit is 131.2 ft (40
m) away from an outdoor unit, select the option “2”.
[328-131.2=196.8 ft(100 - 40 = 60 m)]
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 41
2020-02-14 오전 10:33:41
Summary of Contents for AM0 SERIES
Page 45: ...45 English Appendix Memo AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 45 2020 02 14 오전 10 33 41 ...
Page 46: ...AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 46 2020 02 14 오전 10 33 41 ...
Page 91: ...45 Français Annexe Note AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 45 2020 02 14 오전 10 35 49 ...
Page 92: ...AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 46 2020 02 14 오전 10 35 49 ...