Samsung Electronics
2-45
Model
OAP Duct
AM072JNESCH/AA
AM096JNESCH/AA
Power Supply
φ,V,Hz
1,208~230,60
1,208~230,60
Mode
1)
-
HP
HP
Performance
Capacity
Cooling
2)
Btu/hr 92%
װ
72,000 96,000
Heating
3)
Btu/hr 92%
װ
47,000 59,000
Power
Input Consumption (Cooling/Heating)
W 105%
ײ
360/360
450/450
Running Current (Cooling/Heating)
A 105%
ײ
2.60/2.60
3.10/3.10
Indoorunit refrigerant adding amount
Kg/EA
1.18
1.18
Noise Level
Actual Noise Pressure (High)
dB(A)
ײ
47
47
Fan
Type
-
Sirocco, Φ270*2EA
Sirocco, Φ270*2EA
Motor
Model
-
DL-17860SSBA (DB31-00659A)
DL-17860SSBA (DB31-00659A)
Type
-
BLDC Feedback
BLDC Feedback
Output
W
-
-
Fan Speed
Fan(H/M/L) 0
mmAq
rpm±20
875/-/-
890/-/-
Fan(H/M/L) Standard
1050/-/-
1080/-/-
Cooling (H/M/L)
Standard
-
-
Heating (H/M/L)
Standard
-
-
Airflow Rate
Fan(H/M/L)
᎑
/min
28.00/-/-
35.00/-/-
Cooling (High)
-
-
Heating (High)
-
-
Refrigerant
Type
-
R410a
R410a
Control Method
-
EDM EEV 6.4C
EDM EEV 6.4C
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
External Static Pressure
Standard (Min.~Max)
mmH2O
25(5~30)
25(5~30)
Piping
Connections
Liquid (Flare)
Φ,mm
9.52
9.52
Φinch
3/8
͓
3/8
͓
Gas (Flare)
Φ,mm
19.05 22.23
Φinch
3/4"
7/8"
Drain
Φ,mm
VP25 (OD 32,ID 25) mm
VP25 (OD 32,ID 25) mm
Φinch
-
-
Weight
Net Weight
kg
90
90
Shipping Weight
kg
100
100
Dimensions
Net Dimensions (W×H×D)
mm
1465x460x910
1465x460x910
inch
-
-
Shipping Dimensions (W×H×D)
mm
1612 x 519 x 984
1612 x 519 x 984
inch
-
-
Bypass Tube
SOLENOID VALVE
-
Assy,FDF6A48
Assy,FDF6A48
Check VALVE
-
ID9.6-ID12.9
ID9.6-ID12.9
Panel Size
Model
-
-
-
Net Weight
kg
-
-
Shipping Weight
kg
-
-
Net Dimensions (W×H×D)
mm
-
-
Shipping Dimensions (W×H×D)
mm
-
-
Functions
Auto restart
-
O
O
Auto swing
-
X
X
Group/Individual control
-
O(OAP group only)
O(OAP group only)
External contact control
-
O
O
Trouble shooting by LED
-
X
X
Standard
accessories
Installation manual
-
O
O
Operation manual
-
O
O
Pattern sheet for installation
-
O
O
Flexible drain hose
-
O
O
Filter/Safety grille
-
X
X
Drain pump
Drain pump
- / Model Name
Optional / MDP-G075SQ
Optional / MDP-G075SQ
Max. lifting Height / Displacement
mm / liter/h
750 / 24
750 / 24
Optional
Accessories
Wireless remote controller
-
MR-EH00U
MR-EH00U
Wired remote controller
-
MWR-WE10N
MWR-WE10N
External contact interface module
-
MIM-B14
MIM-B14
Duct Receiver kits
-
MRK-A10N
MRK-A10N
EEV kits
-
-
-
Indoor Unit(cont.)
Q
OAP Duct
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 35
ఁ͑
DB, 28
ఁ͑
WB - Outdoor temperature : 35
ఁ͑
DB, 28
ఁ͑
WB
*3) Norminal heating capacities are based on;
- Indoor temperature : 0
ఁ͑
DB, -3
ఁ͑
WB - Outdoor temperature : 0
ఁ͑
DB, -3
ఁ͑
WB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.