Troubleshooting
Samsung Electronics
91
4-4-43 Digital Compressor Discharge Temperature Sensor Error (OPEN/SHORT)
Yes
Did the connector for the
outdoor digital compressor discharge temperature
sensor break away from the PCB?
Did the resistance value
significantly stray from the following
temperature table?
Separate the connector for the outdoor unit
discharge temperature sensor from the PCB,
and measure the resistance value between
the 2 terminals.
Restart operation after changing PCB.
Restart operation after connecting
the connector to PCB
Change this part as it is the fault of
the discharge temperature sensor itself.
Yes
No
No
Temperature (°C)
130
120
100
80
60
25
20
10
0
Resistance (KΩ)
8.9
11.2
18.5
32.0
59.0
200.0
242.0
362.0
553.0
1. Inspection Method
Resistance value measure part
Outdoor unit display
Indoor unit display
Operation
Timer
Criteria
• Refer to the inspection method below,
Cause of problem
• Digital compressor discharge temperature sensor OPEN/SHORT problem