Samsung Electronics
278
Piping Diagram
Long-piping condition setting
▪
Purpose
Secure performance and reliability when the units are used with long piping.
▪
Concept
-
Control of the compressor frequency, EEV, and valves is optimized to facilitate the circulation of refrigerant in
a long piping condition.
▪
Control specifications in detail
- In heating mode, the initial EEV opening degree increases.
The compressor frequency increase speed decreases if the low pressure is low.
(see "Main EEV control" for details on EEV control).
- In cooling mode, the initial value for target low pressure decreases to 0.7kgf/cm2,g.
(see "Compressor capacity control" for details).
- In cooling mode, EVI bypass mode turns on (see "EVI EEV control" for details).
▪
Notes
- Incorrect settings may seriously damage the system.
- Setting is unnecessary if high-head condition is set.
Input unit
Seg1
Seg2
Seg3
Seg4
Long-piping condition setting
Main
0
9
0
0
Disabled (default)
0
1
Level 1
(When equivalent length of farthest indoor unit
from the outdoor unit is between 100~170m)
0
2
Level 2
(When equivalent length of farthest indoor unit
from the outdoor unit is over 170m)
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)