Troubleshooting
Samsung Electronics
4-3
غ
Auto Trial Operation
ـ͑
After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling
Heating
Method of Entry
K2 Tact Switch twice
K1 Tact Switch twice
Compressor
Normal operation, but the maximum frequency limit (differ by model)
Indoor Unit
Whole operation (The set temperature=3
π
C)
Whole operation (The set temperature=40
π
C)
Outdoor fan and valves
Normally control conduct
Operation time
Min : 60 minutes, Max : 10 hours
Etc.
∙ Exceed the maximum operating time at stops and waits.
∙ Protection and control, self-diagnosis is performed.
غ
Refrigerant filling operation
ـ
Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling
Heating
Method of Entry
K2 Tact Switch one time
K1 Tact Switch one time
Compressor
Starting frequency (Mild Start frequency) operation
Indoor Unit
Whole operation (The set temperature=3
π
C)
Whole operation (The set temperature=40
π
C)
Outdoor fan and valves
Normally control conduct
Operation time
60 minutes
Etc.
During the filling operation does not enter the special operation, such as oil recovery, defrost.
Summary of Contents for AM080*XV Series
Page 205: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN...
Page 208: ...PCB Diagram and Parts List 5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC...
Page 210: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont DC...
Page 216: ...PCB Diagram and Parts List 5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis...
Page 218: ...PCB Diagram and Parts List 5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis...
Page 241: ...Cycle Diagram 7 10 Samsung Electronics 7 16 AM240 260 280 300MXVAGC...