Product Specifications
Samsung Electronics
2-49
Product Specifications
2-48
Samsung Electronics
Outdoor Unit
(cont.)
TYPE
DVM S
Model
AM100MXVDGH/ET
AM120MXVDGH/ET
AM140MXVDGH/ET
AM160MXVDGH/ET
AM180MXVDGH/ET
Power
Ø, #, V, Hz
3, 4, 380-415, 50
3, 4, 380-415, 50
3, 4, 380-415, 50
3, 4, 380-415, 50
3, 4, 380-415, 50
Mode
-
HEAT PUMP
HEAT PUMP
HEAT PUMP
HEAT PUMP
HEAT PUMP
Capacity
HP
HP
10
12
14
16
18
Cooling
kW
28.0 / 28.0*
33.6 / 33.6*
40.0 / 40.0*
45.0 / 45.0*
50.4 / 50.4*
Heating
kW
31.5 / 28.0*
37.8 / 33.6*
45.0 / 40.0*
50.4 / 45.0*
56.7 / 50.4*
Power
Power Input
(Nominal)
Cooling
kW
7.18 / 7.18*
9.36 / 9.36*
12.42 / 12.42*
13.80 / 13.80*
16.00 / 16.00*
Heating
kW
7.50 / 6.67*
9.22 / 8.20*
11.14 / 9.90*
12.63 / 11.28*
14.80 / 13.16*
Current Input
(Nominal)
Cooling
A
11.50
15.00
19.90
22.10
25.70
Heating
A
12.00
14.80
17.90
20.30
23.70
Minimum Ssc
MVA
4.5
5.3
5.4
7.2
8.8
MCA
A
21.1
25.0
25.0
32.0
39.2
MFA
A
32
32
32
40
50
Efficiency
EER
Cooling
W/W
3.90 / 3.90*
3.59 / 3.59*
3.22 / 3.22*
3.26 / 3.26*
3.15 / 3.15*
COP
Heating
W/W
4.20 / 4.20*
4.10 / 4.10*
4.04 / 4.04*
3.99 / 3.99*
3.83 / 3.83*
ESEER
W/W
7.08
6.58
6.60
6.39
5.91
Compressor
Output
kW x n
6.39 x 1
6.39 x 1
6.39 x 1
7.81 x 1
7.81 x 1
Model Name
-
DS-GB066FAV* x 1
DS-GB066FAV* x 1
DS-GB066FAV* x 1
DS4GJ5080FV* x 1
DS4GJ5080FV* x 1
Oil
Type
-
PVE
PVE
PVE
PVE
PVE
Initial charge
cc x n
1,100 x 1
1,100 x 1
1,100 x 1
1,400 x 1
1,400 x 1
Fan
Type
-
Propeller
Propeller
Propeller
Propeller
Propeller
Discharge direction
-
Top
Top
Top
Top
Top
Quantity
EA
1
1
2
2
2
Air Flow Rate
㎥
/min
170
220
255
255
290
l/s
2,833
3,667
4,250
4,250
4,833
External Static
Pressure
Max.
㎜
Aq
8
8
8
8
8
Max.
Pa
78.45
78.45
78.45
78.45
78.45
Fan Motor
Type
-
BLDC Motor
BLDC Motor
BLDC Motor
BLDC Motor
BLDC Motor
Output
W x n
830 x 1
830 x 1
620 x 2
620 x 2
620 x 2
Piping Connections
Liquid Pipe
Type
Braze connection
Braze connection
Braze connection
Braze connection
Braze connection
Φ,
㎜
(inch)
9.52 (3/8)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
15.88 (5/8)
Gas Pipe
Type
Braze connection
Braze connection
Braze connection
Braze connection
Braze connection
Φ,
㎜
(inch)
22.22 (7/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
High pressure Gas Pipe(HR Only)
Type
-
-
-
-
-
Φ,
㎜
(inch)
-
-
-
-
-
Heat Insulation
-
Both liquid and gas pipes
Both liquid and gas pipes
Both liquid and gas pipes
Both liquid and gas pipes
Both liquid and gas pipes
Piping length (ODU-IDU)
Max. [Equiv.]
m
200[220]
200[220]
200[220]
200[220]
200[220]
Piping length (1st Branch-IDU)
Max.
m
90
90
90
90
90
Total piping length (System)
Max.
m
1,000
1,000
1,000
1,000
1,000
Level difference (ODU in highest position)
Max.
m
110
110
110
110
110
Level difference (IDU in highest position)
Max.
m
110
110
110
110
110
Level difference (IDU-IDU)
Max.
m
50
50
50
50
50
Wiring connections
Transmission Cable
㎟
0.75
0.75
0.75
0.75
0.75
Remark
-
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
Power supply intake
-
Both indoor and outdoor unit
Both indoor and outdoor unit
Both indoor and outdoor unit
Both indoor and outdoor unit
Both indoor and outdoor unit
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
5.5
6.5
7.7
8.4
8.4
tCO2e
11.48
13.57
16.08
17.54
17.54
External
Dimension
Net Weight
kg
197.0
210.0
226.0
253.0
255.0
Shipping Weight
kg
204.0
217.0
246.0
273.0
275.0
Net Dimensions (WxHxD)
㎜
880 x 1,695 x 765
880 x 1,695 x 765
1,295 x 1,695 x 765
1,295 x 1,695 x 765
1,295 x 1,695 x 765
Shipping Dimensions (WxHxD)
㎜
948 x 1,887 x 832
948 x 1,887 x 832
1,363 x 1,887 x 832
1,363 x 1,887 x 832
1,363 x 1,887 x 832
Operating
Temp. Range
Cooling
℃
-5 ~ 48
-5 ~ 48
-5 ~ 48
-5 ~ 48
-5 ~ 48
Heating
℃
-25 ~ 24
-25 ~ 24
-25 ~ 24
-25 ~ 24
-25 ~ 24
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.
Summary of Contents for AM080*XV Series
Page 205: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN...
Page 208: ...PCB Diagram and Parts List 5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC...
Page 210: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont DC...
Page 216: ...PCB Diagram and Parts List 5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis...
Page 218: ...PCB Diagram and Parts List 5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis...
Page 241: ...Cycle Diagram 7 10 Samsung Electronics 7 16 AM240 260 280 300MXVAGC...