Product Specifications
Samsung Electronics
2-15
Indoor Unit(cont.)
Q
Big Duct
Model
AM220FNHDEH/TK
AM280FNHDEH/TK
Power Supply
ø/V/Hz
1/220-240/50
1/220-240/50
Mode*
1)
HP / HR
HP / HR
Performance
Capacity
Cooling*
2)
kW
22.4
28.0
Btu/h
76,400
95,500
Heating*
3)
kW
25.0 31.5
Btu/h
85,300
107,500
Condensate (with High fan speed)
Liters/h
Power
Input
W
530
790
Running Current
A
3.8
5.9
Sound Level
Sound Pressure (High/Low)*
4)
dB(A)
47 / 44
48 / 45
Fan
Type
-
Sirocco Fan
Sirocco Fan
Motor
Model
-
DL-13875SSOB
DL-13875SSOB
Type
-
BLDC
BLDC
Output
W
Airflow Rate
Cooling (High)
m
3
/min
58
72
Heating (High)
m
3
/min
58
72
External Static Pressure
Standard(Min.~Max)
mmH
2
O
15(5-25)
15(5-28)
Refrigerant
Type
-
R410A
R410A
Control Method
-
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
9.52
9.52
Gas (Flare)
ø, mm
19.05
22.2
Drain
ø, mm
VP25(OD32, ID25)
VP25(OD32, ID25)
Weight
Net Weight
kg
89
89
Shipping Weight
kg
99
99
Dimensions
Net Dimensions (W x H x D)
mm
1,240x470x1,040
1,240x470x1,040
Shipping Dimensions (W x H x D)
mm
1,507x558x1,155
1,507x558x1,155
Functions
Auto Restart
-
O
O
Auto Swing
-
X
X
Group/Individual Control
-
O
O
External Contact Control
-
O
O
Trouble Shooting by LED
-
X
X
Standard
Accessories
Installation Manual
-
O
O
Operation Manual
-
O
O
Pattern Sheet for Installation
-
O
O
Flexible Drain Hose
-
O
O
Filter / Safety Grille
-
X
X
Optional
Accessories
Wireless Remote Controller
-
MR-DH00
MR-DH00
Duct Receiver
Kits
Receiver
-
MRK-A10
MRK-A10
Receiver Wire
-
MRW-10A
MRW-10A
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
Drain Pump
MDP-N047SNC1D
MDP-N047SNC1D
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.