Installation Procedure
English
Instal
lation Pr
oc
edur
e
•
To protect the product from water and possible shock,
you should keep the power and the communication
cables of the indoor and outdoor units in the iron pipe.
•
Connect the power cable to the auxiliary circuit
breaker (ELCB, MCCB, ELB).
•
Keep distances of 50mm or more between power cable
and communication cables.
•
Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
•
Screws on terminal block must not be unscrewed with
the torque less than 12 kgf•cm.
•
When installing the indoor unit in a computer room,
use the double shielded (tape aluminum / polyester
braid + copper) cable of FROHH2R type.
220~240V~
Outdoor Unit
ELB
MCCB
Indoor Unit 1
Indoor Unit 2
Indoor Unit 3
Indoor Unit 4
Indoor Unit 5
Indoor Unit 6
※
ELB : Essential Installation
※
Ceiling, wall-mounted indoor unit.
EEV kit
Wired Remote
Control
Selecting the crimping terminal lug
1
Select the crimping terminal lug based on the norminal dimension of the power cable.
2
Cover the connection part of the power cable and crimping terminal lug to insulate it.
Silver solder
F
E
L
D
d1
B
d2
t
B
2
R