background image

27

English

Instal

lation Pr

oc

edur
e

Check whether the option values that you have set are 

correct by pressing the   (Mode) button repeatedly

[SEG2, SEG3]

[SEG11 , SEG12 ]

[SEG21 , SEG22]

[SEG4, SEG5]

[SEG14 , SEG15 ]

[SEG23, SEG24]

[SEG6, SEG8]

[SEG16 , SEG17 ]

[SEG9, SEG10]

[SEG18 , SEG20]

Save the option values into the indoor unit:  

Point the remote control to the remote control sensor 

on the indoor unit and then press the   (Power) 

button on the remote control twice. Make sure that 

this command is received by the indoor unit. When it is 

successfully received, you can hear a short sound from 

the indoor unit. If the command is not received, press 

the   (Power) button again.

Check whether the air conditioner operates in 

accordance with the option values you have set:

Reset the indoor unit by disconnecting and then 

reconnecting the power cable of the indoor unit or 

by pressing the RESET button on the outdoor unit.

Remove the batteries from the remote control, 

insert them again, and then press the   (Power) 

button on the remote control.

Setting the indoor unit installation option 

(suitable for the condition of each installation 

location)

Make sure that the power is supplied to the indoor 

unit.

• 

If the indoor unit is not plugged in, it must include a 

power supply.

Make sure that the panel or display is connected to the 

indoor unit so that it can receive options

Indoor unit

Set an address for each indoor unit using the remote 

control, according to your air conditioning system plan.

• 

The indoor unit addresses are set to 020010-

100000-200000-300000 by default.

• 

The SEG20 option, Individual control with remote 

control, allows you to control multiple indoor units 

individually by using the remote control.

DVM TK Wind-Free 1way IM EN_DB68-07553A-00.indb   27

2017-12-01   오후 2:19:09

Summary of Contents for AMxxxNN1DEH Series

Page 1: ...AM NN1DEH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference DB68 07553A 00 DVM TK Wind Free 1way IM...

Page 2: ...the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrigerant pipes Step10 Installing the drain hose and drain pipe Step11 Performing the drainage t...

Page 3: ...r switch theunitoffanddisconnectitfromthepowersupply In orderto prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if...

Page 4: ...that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual Always verify that electric connections cable entry...

Page 5: ...UTION As a rule the unit cannot be installed at a height of less that 2 5m If you install the cassette or duct type indoor unit on the ceiling with humidity over 80 you must apply extra10mm of polyeth...

Page 6: ...let 235 Space of suspension bolts 380 Ceiling opening dimension Model AM017NN1PEH AM022NN1PEH A 134 B 180 Liquid pipe connection 6 35 Gas pipe connection 12 7 Drain hose connection VP20 outer diameter...

Page 7: ...imension 249 Space of suspension bolts 440 Ceiling opening dimension 1036 Space of suspension bolts Model AM022NN1DEH AM028NN1DEH AM036NN1DEH A 130 B 179 Liquid pipe connection 6 35 Gas pipe connectio...

Page 8: ...289 470 Space of suspension bolts 1260 85 35 15 1200 85 A B Ceiling 450 148 34 50 Space of suspension bolts Model AM056NN1DEH AM071NN1DEH A 133 138 B 180 180 Liquid pipe connection 6 35 9 52 Gas pipe...

Page 9: ...tra10 mm thick polyethylene insulation or a similartype of insulation to the body of the indoor unit Cut away the part where pipes are pulled out forthe insulating work Insulate the end of the pipe an...

Page 10: ...to suspend the unit 1 2 2 6 Check the level of the indoor unit by using a leveler A tilt of the indoor unit may cause malfunction of a built in float switch and water leaks Level 7 Adjust the unit to...

Page 11: ...es cut them with a pipe cutter ensuring that the cut edge remains at a 90 angle to the side of the pipe Referto the illustrations below for examples of edges cut correctly and incorrectly Pipe cutter...

Page 12: ...e are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thickness 10 mm or more to prevent condensation even on the insulatorwhen if the installed area is warm and hu...

Page 13: ...e pipes and drain hose avoiding compressing the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connect...

Page 14: ...me insulation that is used for high humidity conditions Geological condition High humidity locations such as shorelines hot springs lake or riversides and ridges when part of the building is covered b...

Page 15: ...y as possible field supply 5 Insulate the whole drain pipe inside the building field supply The whole drain pipe must be insulated with 5t or more insulation to prevent condensation CAUTION Check that...

Page 16: ...pipe Full thread bolt hanger 1000 to 1500 mm 300 to 550 mm 200 mm or more Individual airvent Main airvent must be installed If 3 or more units are installed install the main airvent at the front of t...

Page 17: ...onnect the power supply Reassemble the control box cover c Check whetherthe drain pump works correctly d Check whetherthe drainage is performing correctly at the end of the drain pipe e Check for leak...

Page 18: ...ELEC H07RN F Screws on terminal block must not be unscrewed with the torque less than12 kgf cm When installing the indoor unit in a computer room use the double shielded tape aluminum polyester braid...

Page 19: ...1 s Powercable Earth cable Communication cable 2 5 mm or more 2 5 mm 0 75 to1 5 mm Decide the power cable specification and maximum length by formula 2 1 Decide the capacity of ELB and MCCB by below...

Page 20: ...horten the life of the condenser If the unbalanced power is exceeded over10 of supply rating the indoor unit is protected stopped and the error mode indicates Connectthepowercabletotheauxiliarycircuit...

Page 21: ...ss anothertwo points in the same location The compression dimension should be 8 0 Compression dimension After compressing it pull both sides of the wire to make sure it is firmly pressed Compress it 4...

Page 22: ...insert them again b While holding down the High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are entered to the mode for setting the opti...

Page 23: ...appear on the remote control display 3 Set the SEG4 and SEG5 values a Set the SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display...

Page 24: ...he SEG10 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the follo...

Page 25: ...ol and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote...

Page 26: ...t the SEG22 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the fo...

Page 27: ...and then reconnecting the power cable of the indoor unit or by pressing the RESET button on the outdoor unit b Remove the batteries from the remote control insert them again and then press the Power...

Page 28: ...d with 3 minute delay If you set the Maximum filter usage time SEG18 option to a value otherthan 2 and 6 it is automatically set to 2 1000 hours If you set an option to a value that is out of range sp...

Page 29: ...compensation 5 Use Use Cooling 2 4 Use 10min 1 6 Disuse Use Heating Cooling 2 1 Use 7 Use Use Heating Cooling 2 8 Disuse Use CoolingUltra LowFan 2 2 Highceiling KIT 4way modelonly 6 Use 30min 1 9 Use...

Page 30: ...ation Details Indication Details HeatingSetting Compensation RemovingCondensate WaterinHeatingMode 3 0or1 channel1 0 Default Disuse 0 Default 0 Disuse 1 2 C Disuse 1 Turnoutin30min withoutmotion 2 cha...

Page 31: ...ed on the indoor unit which may fall into a living space use this function to get rid of the water vapor out of the indoor unit by operating the fan for maximum 20 minutes even when the indoor unit is...

Page 32: ...2 1 C 2 1 C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 2 Use Cooling onlyindoor unitforHR 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG1...

Page 33: ...minutes E 6 0 C 20 minutes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE Forcing FAN Operation forHeating and Cooling Indication and Details Indication Details Indication Details Coolin...

Page 34: ...40 60m 3 For MTFC option MTFC Multi Tenant Function Controller kit is required 4 Heater operation when the SEG9 of 02 series installation option is set to using hot water heater orwhen SEG15 is set t...

Page 35: ...for cooling Reference temperature for heating Reference temperature for change from heating to cooling Reference temperature for cooling Cooling thermo off Cooling thermo on Heating thermo off Heatin...

Page 36: ...osition value 0 to 9 Units position value 0 to 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function...

Page 37: ...llow the steps below Afterfinishing the installation of the airconditioner you should explain the following to the user Referto appropriate pages in the User s Manual 1 How to start and stop the air c...

Page 38: ...221 X X X 2 Error on cond sensor E237 3 Error on discharge sensor E251 Other outdoor unit sensor errorthat is not on the above list 1 When there is no communication between the indoor outdoor units fo...

Page 39: ...13 Compressor down due to low pressure sensor prevention control_1 E410 14 Simultaneous opening of cooling heating MCU SOLvalve 1st detection E180 15 Simultaneous opening of cooling heating MCU SOLval...

Page 40: ...o the cushion bottom Put the cushion top onto the indoor unit Put the packing case from the top of set Seal the packing case Unpacking the unit as below procedure Take out the packing case from the se...

Page 41: ...HT 8 0 kg 10 0 kg DIMENSIONS OF THE UNIT WxHxD 740 x135 x 360 mm 970 x135 x 410 mm COUNTRY OF ORIGIN MADE IN KOREA MODEL AM036NN1DEH TK AM056NN1DEH TK AM071NN1DEH TK CLIMATES CLASS T1 T3 T1 T3 T1 T3 R...

Page 42: ...DVM TK Wind Free 1way IM EN_DB68 07553A 00 indb 42 2017 12 01 2 19 12...

Reviews: