3-2-2(i) Refrigerant Adjustment
3-2-2(j) Flare unt fixing torque
Class
At installation
At service
Outter diameter
ø 6.35 mm
(Liquid Side)
ø 9.52 mm
(Gas Side)
ø 12.7 mm
(Gas Side)
ø 15.8 mm
(Gas Side)
160
300
500
700
200
350
550
750
Fixing Torque Final Torque
Torque (kg-cm)
Connection
Pipe Length
5m Max.
5~10m
Air-Purge
Method
Refer to the
detailed Air-Purge
Procedure
Refrigerant
Adjustment
Unnecessary
Add “A” of refrigerant
(R-22) for every 1m.
Air-Purge
Method
Purge air using a
vaccum pump
or an additional
refrigerant cylinder.
Refrigerant
Quantity
refer to
specification sheet
Add “A” of refrigerant
(R-22) for every 1m.
MODEL
24K BTU
18K BTU
“A”
30g
20g