※   In case you want more information about the controllers and accessories, please refer to the Controller and 

Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.

87

11. Installation

Choosing the installation location

If using a multi system, install as described in the 

installation manual supplied with the outdoor unit.

  WARNING

 

Verify that a dedicated circuit breaker and a 

disconnect switch of the appropriate sizes for the air 

conditioner are preinstalled and available for use.

 

Verify that the voltage and frequency of the power 

supply comply with the rated voltage as defined on 

the unit name plate.

 

Verify that a suitable grounding connection is 

available.

 

Do not install this appliance in an environment 

containing hazardous substances or close to 

equipment that releases open flames.

 

• Do not install this appliance near a heater or 

flammable material.

  CAUTION

 

The manufacturer shall not be responsible for 

damage occurring as a result of the wrong voltage 

being applied to this air conditioner.

 

The indoor and outdoor units must be installed in 

compliance with minimum clearances to ensure that 

both units are accessible from both sides and can be 

maintained or repaired. Insufficient clearance may 

reduce product performance, generate excessive 

noise, and reduce the life of some unit components.

  IMPORTANT

 

Any changes or modifications to the installation 

described in this manual that are not expressly 

approved by the manufacturer could void the 

manufacturer’s warranty.

To determine where to locate the indoor and outdoor 

units, you must survey the entire site and consider many 

variables. The goal is to select locations that comply 

with all safety precautions while also minimizing the 

total effort involved.

Indoor unit location requirements

  WARNING

 

Do not install the unit in a humid, oily, or dusty 

location or in a location exposed to direct sunlight, 

water, or rain.

 

Make sure that the wall can support the unit weight.

Examine the area that the customer wants to be air 

conditioned. Consider the following:

 

What wall location will meet minimum clearances 

and provide optimal product performance?

 

Will the wall provide adequate support for the unit 

weight (wall with stud construction or concrete)? If 

applicable, where are the studs?

 

• Where will you place the wall penetration for 

routing the piping bundle (consisting of power and 

communication cables, refrigerant pipes, and the 

drain hose) through the wall to the outdoor unit? Will 

the hole intersect any plumbing or wires in the wall?

 

Is the location as close as possible to where the 

outdoor unit will be installed, to minimize the length 

of piping and cables?

 

Will the condensate drain inside the room, through 

the wall penetration to the outdoor unit, or be 

connected to a condensate pump?

  NOTE

 

This manual covers a typical gravity-drain 

installation where the drain hose is routed to the 

outdoor unit through a hole in the wall.

Minimum clearances for the indoor unit

 

Ceiling

100 mm

125 mm

125 mm

Wall

Summary of Contents for AR TX AWKNEU Series

Page 1: ...Installation RAC forEurope INV R32 50Hz HP Model AR TX AWKNEU Indoor Unit AR TX AWKXEU Outdoor Unit ...

Page 2: ...urope AR7500 19 10 29 Ver 2 0 Released AR9500T RAC new line up TDB AR4500 AR5500 AR9500 19 11 21 Ver 3 0 Released AR9500T RAC new line up TDB AR4500 AR5500 AR7500 AR9500 19 12 13 Ver 3 1 Updated some specification data 20 02 06 Ver 3 2 Updated the Sound data of Outdoor Unit 20 11 25 ...

Page 3: ...eristics C Motion Detect Sensor Wi Fi Tri care Filter E Wi Fi Tri care Filter F Wi Fi H 6 Design Segment A Wind Free GEO C Wind Free AIRISE Y GEO Z AIRISE 7 Version A Z 1 digit 8 Color WK DA White 9 Set N Indoor Unit X Outdoor Unit Set Nomenclature Model Name AR 1 09 2 T 3 X 4 F 5 C 6 A 7 WK 8 N 9 EU Buyer ...

Page 4: ...orUnit Model Type Design Image AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE Model Type Design Capacity kW 2 5 3 5 5 0 6 5 AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE ...

Page 5: ...5 Model Type Design Capacity kW 2 5 3 5 5 0 6 5 AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE Line up OutdoorUnit ...

Page 6: ... 6 Contents 11 Installation 85 ...

Page 7: ...and settles Areawhere animals mayurinate on the product Ammonia maybe generated Do not usethe indoorunitforpreservation offood items plants equipment and artworks This maycause deterioration oftheirquality Do not install the indoorunit if it has anydrainage problem Forthe multi system this indoorunit can be conncected to an R 32 orR 410Aoutdoorunit Check the type of refrigerant in the outdoorunit ...

Page 8: ...ectric and drain Compressor condenser outdoor Unit m Model Pipe length Pipe height Minimum Maximum Standard forfactory charge Maximum 07 09 12 3 15 5 8 18 24 3 30 5 15 CAUTION Outdoor Unit Outerwall Indoor Unit Cut insulation to have rainwater drained Make a U trap A on the pipe which is connected to the indoor unit at outerwall and cut the bottom part of the insulation about 10 mm to prevent rain...

Page 9: ...bed in this manual that are not expressly approved by the manufacturer could void the manufacturer s warranty To determine where to locate the indoor and outdoor units you must survey the entire site and consider many variables The goal is to select locations that comply with all safety precautions while also minimizing the total effort involved Indoorunit location requirements WARNING Do not inst...

Page 10: ...ting the weight of both the L bracket and the outdoor unit If the unit falls it may result in crushing electric shock fire or explosion that could cause death severe personal injury or property damage Installation Guide at the seashore Make sure to follow below guides when installing at the seashore 1 Do not install the product in a place where it is directly exposed to sea water and sea breeze Ma...

Page 11: ...at can block the sea breeze and the height and width of the wall should be 1 5 times larger than the size of the outdoor unit You must secure more than 700 mm of space between the protection wall and the outdoor unit for air circulation Minimum clearances forthe outdoorunit Legends Wall Minimum clearance in mm 600 300 Airflow direction Top view Side view Examples forinstalling one outdoorunit Unit...

Page 12: ...upplied mounting screws and anchors if applicable attach the bracket to the wall Screw Location x 4ea Level Drilling the wall penetration 1 Determine the position of the hole through which the piping bundle consisting of power and communication cables refrigerant pipes and the drain hose will pass Consider the following The hole inner diameter must be 65 mm The recommended hole location is behind ...

Page 13: ... with the outdoor unit WARNING Do not modify the power cable in any way Doing so may cause electric shock or fire due to poor connection poor insulation or current limit override Make sure to comply with the technical standards of electrical installations and the wiring regulations in the local area This appliance must be properly grounded Do not ground the appliance to a gas pipe plastic water pi...

Page 14: ... uses the R 32 refrigerant be cautious not to generate a spark bykeeping the following requirements Do not remove the fuseswith poweron Do not disconnect the powerplug from thewall outlet with poweron It is recommended to locate the outlet in a high position Place the cords so that theyare not tangled 2 Tighten the terminal block screw L1 L2 F1 F2 3 In Step 2 2 step 3 you determined the exit posit...

Page 15: ... the outdoor unit and the ground for installation Ensure that the drained water runs off correctly and safely Allow enough separation distance between the product and the ground 80 mm Estimated snow fall Snow proof hood Ground On the ground 1 Place the outdoor unit in the selected installation location Step 1 1 on page 93 ensuring proper clearances and with the arrow on top of the unit pointing aw...

Page 16: ...odes Adding refrigerant if needed The outdoor unit is charged with sufficient R 32 refrigerant to support up to a 5 m line set For lengths greater than 5 m you must add 15 g of refrigerant per meter of additional length after the lines are evacuated 1 Calculate the additional refrigerant required Additional grams of R 32 Total line set meter 5 15 2 Connect the common hose of the manifold gauge set...

Page 17: ... this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the refrigerant charge label supplied with the product Refrigerant type GWP value R 32 675 GWP Global Warming Potential Calculating tCO e kg x GWP 1000 Indoor unit Outdoor unit Unit Kg tCO e a b c NOTE Factory refrigerant charge of the product see un...

Page 18: ...Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com https partnerhub samsung com Email airconditioner samsung com Images and data in this book may subject to change without prior notice ...

Reviews: