84
SAMSUNG ELECTRONICS
9-2-12 Current sensor error/Input current sensor error
Indoor display
7 SEG DISPLAY
DESCRIPTION
C462
AC Input I_Limit Trip Error
Outdoor display
Current sensor error
Current sensor error
: LAMP ON
: LAMP OFF
: LAMP BLINK
1. Checklist :
1) Is the PFC Shunt("A") resistance value correct? Check the resistor is opened.
2) Is the IPM Shunt("B") resistance value correct? Check the resistor is opened.
3) Is there no short or open around "C"?
2. Troubleshooting procedure
Restart after power
.
Is the PFC shunt and IPM
shunt resistance value correct?
NO
YES
Exchange the Outdoor PBA
Is the current sensor error appeared again?
NO
YES
Terminate the service
Exchange the Outdoor PBA
Summary of Contents for AR07TXCAAWKNEU
Page 49: ...49 SAMSUNG ELECTRONICS 5 2 ASSY KIT CODE DB92 04839Q ...
Page 50: ...50 SAMSUNG ELECTRONICS 5 3 ASSY KIT CODE DB92 04839Q ...
Page 59: ...59 SAMSUNG ELECTRONICS 6 Wiring Diagram 6 1 Indoor Unit CODE DB68 08680A 01 ...
Page 61: ...61 SAMSUNG ELECTRONICS 7 PCB Diagram 7 1 Indoor Main PCB DB92 04839A ...
Page 62: ...62 SAMSUNG ELECTRONICS 7 2 Outdoor PCB DB92 04837A ...
Page 63: ...63 SAMSUNG ELECTRONICS ...
Page 67: ...67 SAMSUNG ELECTRONICS 8 5 DISPLAY PCB DB92 04833B ...