4-5-14 Compressor lock error
1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
�es
Restart after power off.
Is the lock error occurred again?
Is the interphase resistance value of
compressor(u
↔
v, v
↔
w, w
↔
u) normal?
Is the connection cable for the
compressor and power terminal normal?
Exchange the PCB.
Terminate the service.
Exchange the compressor.
Is the compressor body and
interphase resistance insulated?
Exchange the compressor.
Correct the cable connection.
�es
�es
�es
No
No
No