32
■
05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change Over
or Cooling only for HR
only
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling
temp. Offset
(When setting SEG3)
Standard for mode
change Heating
→
Cooling
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication Details
0
5
0
Follow
product
option
0
0 °C
0
0 °C
0
1 °C
1
0.5 °C
1
0.5 °C
1
1.5 °C
1
Use Auto
Change
Over for HR
only
2
1 °C
2
1 °C
2
2 °C
3
1.5 °C
3
1.5 °C
3
2.5 °C
4
2 °C
4
2 °C
4
3 °C
2
Use
Cooling
only indoor
unit for HR
5
2.5 °C
5
2.5 °C
5
3.5 °C
6
3 °C
6
3 °C
6
4 °C
7
3.5 °C
7
3.5 °C
7
4.5 °C
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
change Cooling
→
Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
difference between
indoor units
MTFC (*3)
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
1 °C
0
5min
0
Default
0
Default
1
1.5 °C
1
7min
1
(*1) Height
difference is
more than
30m or
(*2) Distance
is longer
than 110m
2
2 °C
2
9min
3
2.5 °C
3
11min
4
3 °C
4
13min
2
(*1) Height
difference is
15~30m
or
(*2) Distance
is 50~110m
2
Use
5
3.5 °C
5
15min
6
4 °C
6
20min
7
4.5 °C
7
30min
Setting an indoor unit address and installation option
Summary of Contents for Duct Type Series
Page 40: ...DB68 03807A 04...