4-2. Service Operation
4-2-1 Special Operation
■
AM080/100/120/140/160/180/200/220F
S
XV
S
G
S
►
Key input of the outdoor unit when the service enters the operation mode.
K1 (Number of press)
Key operation
Display on segment
1 time
Refrigerant charging in Heating mode
K, 1, BLANK, BLANK
2 times
Trial operation in Heating mode
K, 2, BLANK, BLANK
3 times
Pump out in Heating mode (Outdoor unit address 1)
K, 3, BLANK, 1
4 times
Pump out in Heating mode (Outdoor unit address 2)
K, 3, BLANK, 2
5 times
Pump out in Heating mode (Outdoor unit address 3)
K, 3, BLANK, 3
6 times
Pump out in Heating mode (Outdoor unit address 4)
K, 3, BLANK, 4
7 times
Vacuumig (Outdoor unit address 1)
K, 4, BLANK, 1
8 times
Vacuumig (Outdoor unit address 2)
K, 4, BLANK, 2
9 times
Vacuumig (Outdoor unit address 3)
K, 4, BLANK, 3
10 times
Vacuumig (Outdoor unit address 4)
K, 4, BLANK, 4
11 times
Vacuuming (All outdoor units)
K, 4, BLANK, A
12 times
End Key operation
-
Press and hold 1 time
Auto Trial Operation
K, K, BLANK, BLANK
K2 (Number of press)
Key operation
Display on segment
1 time
Refrigerant charging in Cooling mode
K, 5, BLANK, BLANK
2 times
Trial operation in Cooling mode
K, 6, BLANK, BLANK
3 times
Pump down all units in Cooling mode
K, 7, BLANK, BLANK
4 times
H/R: Checking the pipe connection
H/P: Automatic setting of operation mode (Cooling/Heating)
for trail operation
K, 8, BLANK, BLANK
5 times
Checking the amount of refrigerant
“K” “9” X X (Display of last two digits may
differ depending on the progress)
6 times
Discharge mode of DC link voltage
K, A, BLANK, BLANK
7 times
Forced defrost operation
K, B, BLANK, BLANK
8 times
Forced oil collection
K, C, BLANK, BLANK
9 times
Inverter compressor 1 check
K, D, BLANK, BLANK
10 times
Inverter compressor 2 check
K, E, BLANK, BLANK
11 times
Fan 1 check
K, F, BLANK, BLANK
12 times
Fan 2 check
K, G, BLANK, BLANK
13 times
End Key operation
-
※
When pcb will be replaced or repaired , please shut off the power after carrying out discharge mode without fail
※
When discharge mode is progressing, DC voltage of inverter PBA 1 & inventer PBA 2 indicate on display alternately.
If LED display of inverter PBA 1 & inventer PBA 2 will be turned off and "OK" is displayed, a discharge is completed.
※
If INV error is occurred(E464/364, E461/361, etc.), please wait more than 15 minutes until self-discharging after shutting off the power
because it can not enter a discharge mode.
※
If normal completion discharge mode or self-discharge will be not completed, it is very dangerous to contact because a high DC voltage of
inverter PBA is charged.