Troubleshooting
Samsung Electronics
4-39
4-3-18 Cond Out Temperature Sensor Error (Open/Short)
1. Cause of problem
Yes
Is the COND OUT
sensor connector (CN43) connected
to PCB?
Did the resistance
value significantly stray from the following
temperature table?
After separating the outdoor Cond Out sensor
connector from the PCB, measure the
resistance value between the two terminals.
Restart operation after replace the PCB.
Restart operation after connecting
the connector to the PCB.
Replace this part as it is the defective of
the outdoor Cond Out sensor itself.
Yes
No
No
CN43 (5, 6)
Temperature (°C)
70
60
50
40
30
20
10
0
-10
Resistance (KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
COND
COND
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation Defrost Timer Fan Filter/MPI Operation Defrost Timer Filter Operation Timer Turbo 24
℃
27
℃
◑
×
×
◑
×
◑
×
◑
×
◑
×
×
◑
×
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
∙ Refer to the judgment method below.
Cause of
problem
∙ Disconnection or breakdown of relevant sensor.