Product Specifications
2-16
Samsung Electronics
TYPE
New Model
Comparative Model
Model
AM140FXVAGH
AM160FXVAGH
RD140HHXG
6
RD160HHXG
6
Mode
HP
HP
HP
HP
Power
Ø,V,Hz
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
Capacity
Horse Power
HP
14
16
14
16
Capacity
kW
40.0 45.0 39.2 44.8
btu/h
136,000 153,000 133,800 152,900
Heating
kW
45.0 50.0 44.1 50.0
btu/h
153,000 170,000 150,500 172,000
Power
Power Input
(Nominal)
Cooling 1)
kW
8.90
11.00
-
-
Heating 2)
9.50
11.50
-
-
Current Input
(Nominal)
Cooling 1)
A
14.30
17.60
-
-
Heating 2)
15.20
18.40
-
-
Running
Current
Cooling
A
14.30 17.60 20.90 22.00
Heating
A
15.20 18.40 19.40 27.20
Max.
A
25.00 32.00 29.40 38.30
Power
Consumption
Cooling
kW
8.90 11.00 10.10 12.00
Heating
kW
9.50 11.50 9.65 11.30
MCA / MFA
A
31.3 / 40
40 / 40
-
-
COP
Nominal Cooling
-
4.49
4.09
-
-
Nominal Heating
-
4.74
4.35
-
-
ESEER (HP)
7.02
6.78
-
-
Compressor
Model
-
DS-GB066FA****
DS-GB052FA****
ZPJ83KCE-TFD
ZPI83KCE-TFD
ZPJ72KCE-TFD
ZPI72KCE-TFD
Type
INV x1
INV x2
DVI x1 + FVl x1
DVI x1 + FVl x2
Output
kW
5.80
4.7 x2
5.87 + 5.87
5.16 + 5.16 x2
Lubricant
Type
-
FVC68D
FVC68D
3MAF POE
3MAF POE
Charging
cc
3,900 6,200 4,370 6,540
Refrigerant
Type
-
R410A
R410A
R410A
R410A
Factory Charging
kg
7.7
7.4
7.0
7.0
FAN
Type
-
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Motor Output
W
630 x 2
630 x 2
630 x 2
630 x 2
Airflow rate
᎑ ͠
ΞΚΟ
226
250
226
250
Pipe
Piping
Connections
Liquid
Ø,mm
12.70
12.70
12.70
12.70
Ø,inch
1/2"
1/2"
Gas
Ø,mm
28.58
28.58
25.40
28.58
Ø,inch
1 1/8"
1 1/8"
Dis. Gas
Ø,mm
19.05
22.22
-
-
Ø,inch
3/4"
7/8"
Installation
Limitation
Max.Length
m
200(220)
200(220)
200
200
Max.Height
m
110(40)
110(40)
50(40)
50(40)
Cable
Main
Power(Below/about20m) mm2
4.0 6.0 4.0 6.0
Communication
mm2
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
Set
Dimension
Net Weight
DVM S HP
kg
235.0
278.0
280
329
DVM S HR
214.0
184.0
Shipping
Weight
DVM S HP
kg
254.0
297.0
301
350
DVM S HR
260.0
303.0
Net Dimension(WxHxD)
mm
1295x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
Gross Dimension(WxHxD)
mm
1363x1857x832
1363x1857x832
1363x1912x832
1363x1912x832
Operating
Temp Range
Cooling
DVM S HP
ఁ
-5.0~48.0
-5.0~48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
DVM S HR
-15.0~48.0
-15.0~48.0
Heating
-20.0~24.0
-20.0~24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
Outdoor Unit
(cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.