Product Specifications
Samsung Electronics
2-17
Outdoor Unit
(cont.)
TYPE
New Model
Comparative Model
Model
AM180FXVAGH
AM200FXVAGH
AM220FXVAGH
RD180HHXG
6
RD200HHXG
6
Mode
HP
HP
HP
HP
HP
Power
Ø,V,Hz
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
3/AC380~415/50
Capacity
Horse Power
HP
18
20
22
18
20
Cooling
kW
50.4
56.0
61.6 50.4 56.0
btu/h
171,900
191,000
210,000 171,900 191,000
Heating
kW
56.7
63.0
69.3 56.7 63.0
btu/h
193,500 215,000 236,000 193,500 215,000
Power
Power Input
(Nominal)
Cooling 1)
kW
12.80
15.19
17.35
-
-
Heating 2)
11.90
13.90
16.70
-
-
Current Input
(Nominal)
Cooling 1)
A
20.70
24.40
27.80
-
-
Heating 2)
19.10
22.30
26.80
-
-
Running
Current
Cooling
A
20.70 24.40 27.80 31.30 32.80
Heating
A
19.10 22.30 26.80 26.70 29.10
Max.
A
39.10 42.50 44.50 42.50 44.10
Power
Consumption
Cooling
kW
12.88 15.19 17.35 15.70 17.00
Heating
kW
11.90 13.90 16.70 12.90 14.50
MCA / MFA
A
48.9 / 50
52.5 / 75
52.5 / 75
-
-
COP
Nominal Cooling
-
3.91
3.69
3.55
-
-
Nominal Heating
-
4.76
4.53
4.15
-
-
ESEER (HP)
6.59
6.56
6.25
-
-
Compressor
Model
-
DS-GB066FA****
DS-GB066FA****
DS-GB066FA****
ZPJ83KCE-TFD
ZPI83KCE-TFD
ZPJ83KCE-TFD
ZPI83KCE-TFD
Type
INV x2
INV x2
INV x2
DVI x1 + FVl x2
DVI x1 + FVl x2
Output
kW
5.8 x2
5.8 x2
5.8 x2
5.87 + 5.87 x2
5.87 + 5.87 x2
Lubricant
Type
-
FVC68D
FVC68D
3MAF POE
3MAF POE
Charging
cc
6,200
6,200 6,200 6,540 6,540
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
8.7
8.4
8.4
8.5
8.5
FAN
Type
-
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Pro BLDC
Motor Output
W
630 x2
630 x2
630 x2
630 x2
630 x2
Airflow rate
᎑ ͠ΞΚΟ
270
275
280
270
275
Pipe
Piping
Connections
Liquid
Ø,mm
15.88
15.88
15.88
15.88
15.88
Ø,inch
5/8"
5/8"
5/8"
Gas
Ø,mm
28.58
28.58
28.58
28.58
28.58
Ø,inch
1 1/8"
1 1/8"
1 1/8"
Dis. Gas
Ø,mm
22.22
28.58
28.58
-
-
Ø,inch
7/8"
1 1/8"
1 1/8"
Installation
Limitation
Max.Length
m
200(220)
200(220)
200(220)
200
200
Max.Height
m
110(40)
110(40)
110(40)
50(40)
50(40)
Cable
Main Power(Below/about20m)
mm2
10.0 10.0 10.0 6.0 10.0
Communication
mm2
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
VCTF 0.75~1.5(2P)
Set
Dimension
Net Weight
DVM S HP
kg
300.0
300.0
300.0
340.0
349.0
DVM S HR
306.0
306.0
306.0
Shipping
Weight
DVM S HP
kg
319.0
319.0
319.0
361.0
370.0
DVM S HR
325.0
325.0
325.0
Net Dimension(WxHxD)
mm
1295x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
Gross Dimension(WxHxD)
mm
1363x1857x832
1363x1857x832
1363x1857x832
1363x1912x832
1363x1912x832
Operating
Temp Range
Cooling
DVM S HP
ఁ
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0~ 48.0
-5.0 ~ 48.0
DVM S HR
-15.0~48.0
-15.0~48.0
-15.0~48.0
Heating
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.