8-
2
Sa
msun
g
El
ec
troni
c
s
S
W58
K21 K22
K21 K22
TE
N
ON
E
MC
U
0
1 2 3
4
5
6
7
8
9
A
B
C
D
E F
Switch
Setting
Function
Remarks
S
W51/
S
W5
2
Se
ttin
g
tot
a
l num
be
r o
f
inst
a
ll
ed
in
d
oor unit
S
W51: T
e
ns
d
i
g
it,
S
W5
2
: Units
d
i
g
it
Se
ttin
g
ca
n
be
d
on
e
f
rom th
e
m
a
in out
d
oor unit only
(su
b
unit: s
e
ttin
g
is unn
ece
ss
a
ry)
Ex) Wh
e
n 1
2
in
d
oor units
a
r
e
inst
a
ll
ed
→
S
W51: 1,
S
W5
2
:
2
K5
ON
H/P(H
ea
t Pump)
S
yst
e
m
Conn
ec
t Li
g
ui
d
pip
e
a
n
d
Hi
g
h pr
e
ssur
e
ga
s pip
e
OFF
HR(H
ea
t R
ec
ov
e
ry)
S
yst
e
m
Clos
e
out
d
oor unit's h
ea
tpump v
a
lv
e
K6
ON
En
ab
l
e
m
a
ximum
ca
p
ac
ity r
e
stri
c
tion
f
or
c
oolin
g
op
e
r
a
tion
R
e
stri
c
t
e
x
ce
ssiv
e
ca
p
ac
ity in
c
r
ea
s
e
wh
e
n op
e
r
a
tin
g
in
d
oor
units with sm
a
ll
ca
p
ac
ity
OFF
Dis
ab
l
e
m
a
ximum
ca
p
ac
ity r
e
stri
c
tion
f
or
c
oolin
g
op
e
r
a
tion
-
K7
K8
Se
l
ec
tin
g
out
d
oor unit
add
r
e
ss
ON
ON
Out
d
oor unit
add
r
e
ss: No 1
M
a
in unit
ON
OFF
Out
d
oor unit
add
r
e
ss: No
2
S
u
b
unit 1
OFF
ON
Out
d
oor unit
add
r
e
ss: No
3
S
u
b
unit
2
OFF
OFF
Out
d
oor unit
add
r
e
ss: No 4
S
u
b
unit
3
S
W57
Se
ttin
g
tot
a
l num
be
r o
f
c
onn
ec
t
ed
MCU
Se
ttin
g
ca
n
be
d
on
e
f
rom m
a
in unit only
Ex) Wh
e
n
3
MCUs
a
r
e
inst
a
ll
ed
→
S
W57:
3
,
S
W5
2
:
2
S
W58
K
2
1
K
22
Se
l
ec
tin
g
typ
e
o
f
c
ir
c
ul
a
tin
g
w
a
t
e
r
ON
ON
W
a
t
e
r
c
ir
c
ul
a
tion
-
ON
OFF
Anti-
f
r
ee
z
e
c
ir
c
ul
a
tion (
f
r
ee
zin
g
point o
f
a
nti-
f
r
ee
z
e
must
be
be
low -8 °C)
Minimum t
e
mp
e
r
a
tur
e
o
f
e
nt
e
rin
g
w
a
t
e
r -5 °C
OFF
ON
Anti-
f
r
ee
z
e
c
ir
c
ul
a
tion (
f
r
ee
zin
g
point o
f
a
nti-
f
r
ee
z
e
must
be
be
low -15 °C)
Minimum t
e
mp
e
r
a
tur
e
o
f
e
nt
e
rin
g
w
a
t
e
r -10 °C
※
M
a
int
a
in
a
ppropri
a
t
e
c
on
ce
ntr
a
tion l
e
v
e
l o
f
a
nti-
f
r
ee
z
e
acc
or
d
in
g
to
S
W58 swit
c
h s
e
ttin
g
.
㽞
AM080/100/120/200FXWA
66
※
I
f
you inst
a
ll HR pro
d
u
c
ts, you must m
a
t
c
h th
e
add
r
e
ss
be
tw
ee
n th
e
MCU
a
n
d
th
e
in
d
oor unit.